background image

Installation Instructions

Model # ONW-P-1001-MV-W
Model # ONW-P-1001-MV-V
Model # ONW-P-1001-MV-LA
Model # ONW-P-1001-MV-G
Model # ONW-P-1001-MV-B

NeoSwitch Passive Infrared (PIR) 

Single Relay Occupancy Sensing Wall Switch

(Ground Required)

• Read all instructions on both sides of this sheet first.
• Install in accordance with ALL local codes.

• For indoor use only.

General Information

Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com 

Technology:

Passive Infrared (PIR)

Electrical Ratings   

120 VAC:

• Incandescent/Tungsten  –  Max.  load:  6.7  amps,

800W, 50/60 Hz

• Fluorescent/Ballast – Max. load: 10 amps, 1200W,

50/60 Hz

Motor Load: ¼ HP @ 125 VAC
277 VAC:

• Fluorescent/Ballast  –  Max.  load:  9.8  amps,

2700W, 50/60 Hz

Ballast  Compatibility:

Compatible  with  magnetic  and

electronic ballasts

No Minimum Load Requirement
Time  Delays:

Self-Adjusting,  15  seconds/test  (10  min

Auto), Selectable 5, 15, 30 minutes

Coverage:

Major motion – 1000 sq. ft.

Minor motion –  300 sq. ft.

Light Level Sensing:

0 to 200 foot-candles

Operating Environment:

• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% Non-condensing

Housing:

Durable,  injection  molded  housing.

Polycarbonate resin complies with UL94VO.

Size:

• Mounting Plate/Strap Dimensions:

4.195" H x 1.732" W (106.553 mm x 44 mm)

• Product  Housing  Dimensions:  2.618"  H  x  1.752"

W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)

LED  Indicators:

Red  LED  indicates  PIR  detection;

Green LED acts as EcoMeter or night light locator.

Specifications

Description

Coverage

The ONW-P-1001-MV Occupancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing lighting control

and conventional Wall Switch all-in-one, used for energy savings and convenience.

PIR Technology

The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature

that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.  

The ONW-P-1001-MV allows the control of one load with one occupancy sensor switch.  

The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.

In Automatic ON Mode, the lights turn ON automatically when a person enters the room.   In Manual ON Mode,

the lights are turned ON by pressing the universally recognized light icon Pushbutton.  In either mode, the lights stay

ON as long as the sensor detects motion in the room.  When the room is vacated, the lights turn OFF automatically

after a preset Time Delay interval.

The  sensor  includes  self-adaptive  technology  that  continually  adjusts  to  conditions  by  adjusting  sensitivity  and

Time Delay in Real-time.  By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the poten-

tial energy savings that are available in the particular application.

The  EcoMeter  provides  a  visual  indicator  of  energy  usage,  increasing  end  user  awareness  and  reminding

individuals to take control of their lighting to maximize energy savings.

The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.  

Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy.  The

sensor will switch the lights ON when it detects a person entering the area.  If the sensor does not continue to detect

motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.

The ONW-P-1001-MV is designed for offices up to 300 square feet.  Coverage testing has been performed according

to the NEMA WD7 Guideline.

Location

When  installing  the  ONW-P-1001-MV  in  a  new  junction  box,  choose  the  switch  location  carefully  to  provide 

optimum  coverage  of  the  occupied  area.    When  replacing  an  existing  Wall  Switch,  bear  in  mind  that  there  must  be  a 
clear Line-of-sight between the sensor and the area to be covered.  Avoid pointing the ONW-P-1001-MV directly into the hall-
way where it may detect passers-by.

EcoMeter Operation

Load 1

EcoMeter LED

OFF

ON

ON

OFF

Action   

EcoMeter

Benefit

A person enters the space and

the load is activated

OFF

The area is vacated and the

lights turn OFF automatically

100%

Increased awareness of energy savings; 

Acts as a night light locator

A person turns the lights OFF

manually upon exiting an area

100%

Increased awareness of energy savings and

reminds individuals to take control of their 

lighting for additional savings;  Acts as a night

light locator

The daylight feature prevents

the lights from automatically 

turning ON when a person

enters an area

100%

Increased awareness of energy savings and

lets individual know that the daylighting

feature is working

Wiring

CAUTION:  Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker.  According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.”  All installations should
be in compliance with the National Electric Code and all state and local codes.

NOTE  REGARDING  COMPACT  FLUORESCENT  LAMPS:    The  life  of  some  compact  fluorescent  lamps  (CFLs)  is

shortened by frequent automatic or manual switching.  Check with CFL and ballast manufacturer to determine the
effects of cycling.

1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. 
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments.  (See Checkout and Adjustments section)
6. Install Wall Switch plate.

LOAD

120/277 VAC

BLACK

BLUE

NEUTRAL

GROUND

GREEN

Wiring Diagram 1:

120/277 VAC single level single circuit wiring diagram

Installation

The  ONW-P-1001-MV  can  be  installed  in  any  standard  single  gang

box.  It may be installed in the same manner as an ordinary Wall Switch.

• Wire the ONW-P-1001-MV as described in the wiring section.
• Mount the ONW-P-1001-MV in the junction box.

,

36

20

,

Maximum coverage area may

vary somewhat according to room

shape and the presence of obstacles.

8

,

Minor Motion, IR

Major Motion, IR

Reviews: