background image

Limited Warranty

DIP Switch Settings 

Troubleshooting

All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in
material and workmanship and shall conform to and perform in accordance with Seller’s written specifications for a period of: Five
(5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and
software on Lighting Control Panels.  We warranty all our standard relays for a period of 10 years from date of factory invoice.  We
guarantee  the  performance  of  our  system  to  specifications  or  your  money  back.    This  warranty  will  be  limited  to  the  repair  or
replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller.  This limited
warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage
during  shipment  or  by  improper  service.    There  are  no  warranties,  which  extend  beyond  the  hereinabove-limited  warranty,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS.
No employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller
any other liability in connection with any of its goods except in writing and signed by the Seller.  The Seller makes no representa-
tion that the goods comply with any present or future federal, state or local regulation or ordinance.  Compliance is the Buyer’s
responsibility.  The use of the Seller’s goods should be in accordance with the provision of the National Electrical Code, UL and/or
other industry or military standards that are pertinent to the particular end use.  Installation or use not in accordance with these
codes and standards could be hazardous.

Cooper Controls
203 Cooper Circle, Peachtree City, GA 30269
800-553-3879
www.coopercontrol.com 

P/N 910-0539     
REV B

Checkout and Adjustment 

LOAD 1

120 to 277 VAC

BLACK

BLUE

NEUTRAL

GROUND

GREEN

WHITE

LOAD 2

A/B SWITCHING USING TOGGLE 

SWITCH TO TURN OFF SECOND LOAD

LOAD 1

BLACK

BLUE

NEUTRAL

THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.

GROUND

GREEN

WHITE

120 to 277 VAC

BLACK

BLUE

GROUND

GREEN

WHITE

TRAVELER 
WIRES

Wiring Diagram 3: 

120 to 277 VAC single level single circuit three-way wiring diagram

Wiring Diagram 2:

120 to 277 VAC single level
switch dual level wiring using a
toggle switch wiring diagram

as the self-adjusting feature is enabled, the switch will respond to each pair of False-offs with no normal off in between
by alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so there should be
no need for manual adjustment.  If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend.
Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down.  (If DIP Switches 1 and 2 are
already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)  

Override

The override setting allows the sensor to operate as a service switch in the unlikely event of failure.

1. Move DIP Switch 8 up.

2. The Pushbutton can be used to manually turn lights ON or OFF. 

1 2 3 4 5 6 7 8 9 10 11 12

Not Used

5 Minutes

Auto*

*Self-Adjusts to

10 min. user mode

Time Delay

DIP Switch

Activation

PIR Sensitivity

Override

Relay 1

EcoMeter

Walk-Through Mode

Default = 

30 Minutes

15 Minutes

1

2

DIP Switch Legend

6

q
p

Disable

Enable

3

q

q

q

q
q

p

p

p

p

p

Auto

Manual

5

q
p

Full

50%

8

q
p

p

q

7

Enable

Disable

4

Disable

Enable

Not Used

Maintain Lights On

Not Used

12

11

9

10

q
p

Either

Both

Adjustments should be made with the HVAC system on so that the installer will be able to detect the effect of air-

flow on the operation of the ONW-D-1001-MV-N.  Use only insulated tools to make adjustments.

Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power up

and stabilize.

Self-Adjust Mode

 Sensor is shipped in self-adjust mode.  This applies to

Time Delay, US and PIR sensitivity.  In preparation for the
Installer Test, the Time Delay is set to 15 seconds, after the
sensor is installed, powered ON and has stabilized, the unit
will Time-out 15 seconds after the last motion detected.
Coverage and sensitivity can be confirmed by watching the
Green (US) and Red (PIR) indicator LEDs on the front of the
sensor, while moving around the room.  

1. Walk around the room and monitor LEDs.  
2. Stand in different parts of the room and wave your 

hands.  LEDs should only turn ON for one second with 

each motion.  (If LEDs do not turn ON, go to Installer Adjustments – Sensitivity Adjustment Section)

3. Stand  still  three  to  four  feet  away  from  sensor  for  five  seconds.    LEDs  should  not  turn  ON.  (If  any  LED  turns  ON, 

note LED and go to Installer Adjustments – Sensitivity Adjustments section)

4. Walk  outside  the  room  and  wait  15  seconds  for  the  lights  to  turn  OFF.  (If  lights  do  not  turn  OFF  go  to  Installer 

Adjustments Section)

5. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
6. At this point you can exit the room and let the sensor Time-out.  When the sensor times-out and is inactive for five 

minutes, the unit will go to a 10 minute Time Delay user mode setting.

Note:

To place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds, and then back in to its original position. 

Installer Adjustments

Sensitivity Adjustments

Ultrasonic  Sensitivity  (Green  LED)  –  Using  a  small  flathead  screw  driver  turn  the
green potentiometer so that the arrow points UP.  

1. Stand in different areas of the room and wave your hands.  
2. If  the  Green  LED  does  not  turn  ON,  increase  the  US  sensitivity  by  turning  the 

green potentiometer clockwise in small increments.  Repeat Step 1.

3. Stand  still  three  to  four  feet  away  from  sensor  for  five  seconds.    LED  should 

not turn ON. 

4. If  Green  LED  turns  ON  without  motion  or  is  constantly  ON  decrease  the  US 

sensitivity  by  turning  green  potentiometer  counter-clockwise  in  small 
decrements. Repeat Step 3.

Note:

Do Not adjust sensitivity higher than necessary.

PIR Sensitivity

1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still three to four feet away from sensor for five seconds.  LED should not turn ON.
4. If Red LED turns ON without motion or is constantly on adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.

ON/OFF Disabled Feature

1. ON/OFF Button Disable Option – When selected this option disables the ON/OFF button and sensor becomes automatic 

only control regardless of the setting for automatic or manual activation.  This feature will not allow someone to turn 
light(s) OFF via the Pushbutton while people are in common areas such as restroom, break room, and copy room areas.

Field-of-view outside the space

1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
2. Use non-reflective tape strips to cover the portions of the 

sensor lens that view outside the space.

3. Adjust Ultrasonic Sensitivity.

Daylight Adjustments

The  daylighting  feature  prevents  the  lights  from  turning  ON

when the room is adequately illuminated by natural light.  If there
is enough light in the room regardless of occupancy, the sensor will hold the lights OFF.  If there is not enough light in the
room, the sensor will allow the lights to turn ON when occupied.  The sensor will not allow the daylighting feature to turn the
load OFF until the space is vacant or the light level rises above the setpoint and the Time Delay expires.  While in Manual
Activation Mode, if someone attempts to turn the load ON and there is sufficient daylight available the Daylighting feature will
hold the lights OFF. 

• Set the light level when the ambient light is at the level where no artificial light is needed.  If this feature is not needed,  

leave the light level at maximum (fully CW). 

1.  With the load(s) ON, put the sensor into Test Mode.  To place into Test Mode, toggle DIP Switch 12 out of its current            

position, wait 3 seconds and then back in to its original position.    

2. Set the Light level to minimum (fully CCW). 
3. Let the sensor Time-out so lights are OFF. Enter the space and lights should remain OFF. 
4. Make sure not to block the sensor from the daylight source and

adjust the light level potentiometer CW in small incre-
ments. (Pause 5 seconds between each adjustment) 

5. Once the lights are ON, the load connected to the sensor will 

not turn ON if light levels are above the current illumination.

Time Delay Adjustments

People who remain very still for long periods of time may need a

longer Time Delay than the default setting of 10 minutes.  As long

ON/OFF Button

PIR Lens

DIP Switches

Ultrasonic Detection

Daylight 

Sensor Level 

Adjustment

Ultrasonic 
Sensitivity 

Adjustment

Red (PIR) & Green (US) 

Detection LEDs

 

 

1 2 3 4 5 6

7 8 9 10 11 12

1 and 2

1 2 3

4 5 6 7 8 9 10 11 12

Issue

Possible Causes

Suggestions

Lights 

Will Not

Turn ON 

automatically

Sensor is in Manual ON mode

Press Pushbutton. If Auto Mode

is desired change Activation Mode to Auto.

Sensor was turned OFF manually.  If the Sensor

was turned OFF manually before the Time Delay
expired, lights will remain OFF for the remainder 

of the Time Delay.  

Check EcoMeter LED.  If LED is ON this is 

an indication that the lights were turned OFF manually.  

Press the Pushbutton to turn the lights back ON.

Daylight Feature Enabled

If all lights are required to turn ON 

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring.

Lights 

Will Not 

Turn ON 

manually

Daylight Feature Enabled

If all lights are required to turn ON 

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring.

If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879

Lights 

Will Not 

Turn OFF 

automatically

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up).

Self-Adjust

If sensor is in Self-Adjust Mode, it may be possible for the

unit to have increased the Time Delay to a 30 minute delay.  

If the lights do not turn OFF after 30 minutes follow next step.

30 Minute Delay

Maximum Time Delay is 30 Minutes.  Check DIP Switches 

to verify DIP Switch settings.  If lights do not turn OFF at the

set Time Delay, check next step.

Ultrasonic Sensitivity set High

Lower sensitivity by turning green 

potentiometer CCW in small decrements.

PIR activated by heat source other than occupant

Move DIP Switch 5 up.

Lights 

Will Not 

Turn OFF 
manually

Call Technical Services

If lights will still not turn OFF, call Technical Services at 1-800-553-3879

Printed in Malaysia

CAUTION:  If a room is wired for two circuits using two separate hot leads, it is very important to connect only
one circuit per relay.  Both circuits must be fed from the same phase.

Reviews: