Installation Instructions

Description

Model # OEC-U-0701-25-AF
Model # OEC-U-0701-AF
Model # OEC-U-1500-25-AF
Model # OEC-U-1500-AF

Standard Ultrasonic Airflow Tolerant Sensor

10-30 VDC

• Read all instructions on both sides of this sheet first.
• Plan all component locations carefully.
• Install in accordance with ALL local codes.
• For use with Greengate Switchpacks & Systems Only.  For use with other systems, 

contact Technical Support.

• Not for use where temperatures fall below 60°F or above 90°F.
• For indoor use only.
•  DO  NOT  run  any  Greengate  low  voltage  wiring  in  the  same  conduit  as  power 

conductors.

General Information

Cooper Controls
203 Cooper Circle, Peachtree, GA 30269
800-553-3879
www.coopercontrol.com 

Designed  to  resist  false  activations  in  high  airflow  applications,  the  OEC-U-XXXX-AF  is  an

ultrasonic motion sensor with built-in timing and load control relay driving circuitry.  The sensor
produces  a  low  intensity,  inaudible  sound.    It  detects  changes  in  the  sound  waves  caused  by
motion,  such  as  walking  into  a  room,  raising  a  hand  in  class,  turning  in  a  swivel  chair,  etc.
Model  OEC-U-XXXX-AF,  with Airflow Tolerant  Circuitry

(TM)

,  reacts  only  to  the  portion  of  the  fre-

quency  spectrum  which  contains  object  motion  while  filtering  the  portion  which  relates  to  air
movement.  When the sensor detects motion, the pre-set time delay period is started and the
blue wire is electronically connected to the red wire.  This energizes the relay in the switchpack
which turns on the load.  At the end of the pre-set time period, the blue wire is disconnected
from the red, causing the relay to open which turns off the load.  The red lead is +15 VDC sup-
ply, the black lead is common and the blue is the relay control.

Product Mounting Location

Sensor:

Choose the sensor location carefully.  The sensor must have a clear view of the area to be con-

trolled. It should not be blocked from “seeing” people by high partitions.  The sensor will not “see”
through glass.  Mounting height should be kept below 12 feet.  Avoid pointing into hallways. To
prevent false activation, the sensor should be 4-6 feet mounted away from the path of strong air
turbulence.  For indoor use only.  For typical placement, refer to the Location Diagrams.

If  partitions  between  49”  to  71”  are  present,  see  Coverage  Diagrams.    For  greater  partition

heights, each partitioned area should be treated as an individual space with floor to ceiling walls.
Additional Greengate sensors may be used to extend the coverage of the OEC-U-XXXX-AF.

Switchpack:

The  switchpack  is  generally  mounted  above  the  ceiling  on

the outside of the junction box that contains a hot line, neutral
and the existing switch leg from which the lighting is controlled.  
If additional switchpacks are required, they are mounted on the
outside  of  the  boxes  containing  the  appropriate  switch  legs.      
In  installations  where  there  are  no  existing  switch  legs,  the
switchpack may be mounted on the outside of any conventional
standard junction box, with or without an extension ring.

Coverage Diagram

Minor

Major

OEC-U-0701-25-AF

OEC-U-0701-AF

OEC-U-1500-25-AF

OEC-U-1500-AF

CAUTION:

Before installing or performing any service on a Greengate system, the power MUST

be  turned  off  at  the  branch  circuit  breaker.   According  to  NEC  240-83(d),  if  the  branch  circuit
breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be
marked “SWD.” 

NOTE  REGARDING  COMPACT  FLUORESCENT  LAMPS:

The  life  of  some  compact  fluorescent

lamps  (CFLs)  is  shortened  by  frequent  automatic  or  manual  switching.    Check  with  CFL  and 
ballast manufacturer to determine the effects of cycling.

Model 

Coverage 

Field of View 

Frequencies

OEC-U-0701-AF

Up to 700 sq. ft. 

180° (One Way)

25, 27kHz

OEC-U-1500-AF

500 to 1,500 sq. ft.

360° (Two Way)

25, 27kHz

OEC-U-0701-25-AF/OEC-U-0701-AF

OEC-U-1500-25-AF/OEC-U-1500-AF

Multiple Frequencies:

Large open areas can be divided into individually controlled spaces without gaps in coverage.

Each  adjacent  area  can  be  independently  controlled  by  using  alternate  frequency  sensors.
Available frequencies are: 25 kHz and 27 kHz(Standard).  Coverages vary.  Please consult the
OEC-U tech sheet or consult with Greengate Technical Support.

NOTE:

Use Model OEC-U-0701-AF in areas from up to 700 square feet. See Coverage Diagrams. The OEC-U-0701-AF sensor is NOT designed

for corridor or warehouse applications. Refer to Greengate Tech Sheets for the appropriate Corridor/Warehouse sensor and for areas outside the
OEC-U-0701-AF coverage range.

NOTE:

Use  Model  OEC-U-1500-AF  in  areas  from  700  to  1,500  square  feet.  See  Coverage  Diagrams.  The  OEC-U-1500-AF  sensor  is  NOT

designed for corridor or warehouse applications. Refer to Greengate Tech Sheets for the appropriate Corridor/Warehouse sensor and for areas
outside the OEC-U-1500-AF coverage range.

Minimum

Sensitivity

Range

Minutes

Maximum

Sensitivity

15

Seconds

30

Minutes

All coverage patterns verified using NEMA WD-7 testing guidelines.  Dimensions are in feet
(meters).  Products  tested  at  10’  (3.048m)  height.    Recommended  standard  frequency  is
27kHz.

27'

18'

22'

16'

27'

16'

25'

20'

61'

25'

23'

35'

28'

46'

13'

20'

S

S

S

18’

10’

L-SHAPED
OFFICE

10’ X 12’ OFFICE

15’ X 20’ CONFERENCE ROOM

S

SENSOR