7 PRODUCT
CHV
5 COM PACT MULTI VRF UNIT
SERVICE M ANUAL
setting is 16
℃
for cooling and 30
℃
for heating).
a. Variance ratio of cooling capacity
25
0.97
Hm(m)
20
10
Hp(m)
1.0
10
10
20
40
20
30
50
60
L(m)
80
70
90
100
0.95
0.92
0.90
0.85
0.87
b Var iance ratio of heating capacity
20
10
Hm(m)
10
10
Hp(m)
20
25
20
30
50
40
60
1.0
70
90
80
100
L(m)
0.97
0.92
0.9
Under heating operation, it may frost w hen there is snow on the outdoor heat exchangers or the outdoor
temperature is below 6
℃
, which will reduce the heating capability of the unit.
5.1 System Flowchart
As the following system flowchart, princilple of operation is :
Conneting to power supply, the uint stars to work.In cooling, the low-temperature and low-pressure refrigerant
gas from each indoor heat exchanger will be merged and inhaled by the compressor and then become
high-temperature and high-pressure gas, which will later be discharged into outdoor heat exchangers. By
exchanging heat with outdoor air, refrigerant will turn to liquid and flow to each indoor unit via Y-type branch or
manifold. Pressure and temperature of the refrigerant will then be lowered by throttle elements before it flows into
indoor heat exchangers. After exchanging heat with indoor air, refrigerant wil become low -temperature and
low-pressure gas again and repeat the circulation so as to realize the cooling effect. In heating, 4-way valve will be
energized to make refrigerant circulate in a reverse direction of cooling. Refrigerant will release heat in indoor heat
exchangers (electric heating elements will also work under certain circumstance and release heat) and absorb heat
in outdoor heat exchangers circularly so as to realize the heating effect.
Summary of Contents for CHV-5S224SNMX
Page 1: ...CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL R410A 50 60Hz...
Page 3: ...1 PRODUCT CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL PRODUCT...
Page 11: ...0 900 CONTROL CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL CONTROL...
Page 50: ...INSTALLATION 0 48 0 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL INSTALLATION...
Page 74: ...MAINTENACE 0720 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL Maintenace...
Page 120: ...MAINTENACE 01180 CHV5 COMPACT MULTI VRF UNIT SERVICE MANUAL...