4 Analog Usage
4.1 Analog input type
Input signal type
Range
Register
reading value
Resolution
Accuracy
total range
E type thermocouple
Environment
temperature
~599.9
℃
Room
temperature~5
999
0.1
℃
1%
K type
thermocouple
Environment
temperature
~999.9
℃
Room
temperature~9
999
0.1
℃
1%
J type thermocouple
Environment
temperature
~999.9
℃
Room
temperature~9
999
0.1
℃
1%
Thermistor
NTC10K
-19.9~109.9
℃
-199~1099
0.1
℃
1%
Thermistor
NTC50K
-40~199.9
℃
-400~1999
0.1
℃
1%
Voltage analog
0~10V/0-5V
0~4000
2.5mV
1%
Current analog
0~20mA
0~4000
5uA
1%
4.1.1 Analog input reading
Analog input could be up to 4 channels, and the precision is in 12 bits.
NO
Register reading
value
AD0
D8030
AD1
D8031
AD2
D8032
AD3
D8033
AD4
D8034
AD5
D8035
AD6
D8036
AD7
D8037
AD8
D8038
AD9
D8050
AD10
D8051
AD11
D8052