When the analog input has a thermocouple type, it can only do up to 15 channels, of which AD4 is the
ambient temperature of the thermocouple. You can do 16 channels without the thermocouple type.
Tthermistor NTC is shown as below table:
NO
Register Value
AD0
R23660
AD1
R23661
AD2
R23662
AD3
R23663
AD4
R23664
AD5
R23665
AD6
R23666
AD7
R23667
AD8
R23668
AD9
R23669
AD10
R23670
AD11
R23671
AD12
R23672
AD13
R23673
AD14
R23674
AD15
R23675
R23960 starts with a zero correction value and default is 0 (Namely, size correction).
R23980 starts with a negative temperature amplification. The default is 4633 (temporarily only have
negative temperature amplification).
The 16 registers starting from R23620 are 0~10V or 0~20mA corresponding values, that is, real-time
sampled values.
2.6.5 Analog input sampling
Filtering cycles=( R23600~R23615)* PLC scanning time, if R23600=1, One PLC scan cycle sample
one time and change the 1
st
analog input value for one time. The larger R23600~R23615 value is, the result
is more stable.
R23600~R23615 is filtering cycles, default is 100 (range 2~20000), data can’t be equal to or less than 0;
D8073 is smoothing filter coefficients of all analog input, range: 0~999