ASCII I/F
CoolMasterNet PRM Rev 0.7
37
www.coolautomation.com
© 2017 CoolAutomation
swing
SYNOPSIS
swing [
] <h|v|a|3|4|6|x>
DESCRIPTION
Set Indoor Unit(s) louver position to:
·
h - horizontal
·
v - vertical
·
a - auto (swing)
·
3 - 30º
·
4 - 45º
·
6 - 60º
Not all Indoor Units support louver position options listed about or have louver position control at all. Louver
control is capability of the specific Indoor Unit type. If requested louver position is not supported by Indoor
Unit(s), swing command will have no effect or will return an error.
EXAMPLE
Set Indoor Unit 102 on line L1 louver to horizontal position
>
swing L1.102 h
OK
Set all Indoor Units louver to 30º position
>
swing 3
OK
filt
SYNOPSIS
filt [
DESCRIPTION
Reset Filter Sign.
EXAMPLE
Reset Filter Sign on Indoor Unit 102 0n line L1
>
filt L1.102
OK
Reset Filter Sign on all Indoor Units on Line L2
>
filt L2*
OK
Reset Filter Sign on all Indoor Units
>
filt
OK
stat
SYNOPSIS
stat [
stat2 [
]
stat3 [
]