15
www.coolautomation.com
CooLinkHub PRM 1.0
© 2017 CoolAutomation
ASCII I/F
aserver prompt R/W
aserver prompt 0 or 1
Aserver prompt control:
0 - prompt disabled
1 - prompt enabled
deg
R/W
deg C/F
C or F
Temperature scale Celsius or Fahrenheit
melody
R/W
melody
string
Power-up melody. The value is printed as
melody name, to change the melody its
number should be provided.
set melody
command lists supported
melodies and their numbers.
filter of visi
R/W
filter
visi_0 or
visi_1 or
"-"
Indoor units visibility according to
"-" - visibility filter applies only to LCD
1
- visibility filter applies to LCD and
status/control commands
0 - visibility logic is inverted and filter is
applied to LCD and status/control
commands
HVAC lines
RO
HVAC lines
0...8
Maximal allowed number of HVAC lines.
max indoors
RO
max indoors
1..256
Maximal number of supported indoor units
reset on assert RO
rst on assert
0 or 1
Determines whether CooLinkHub will
restart or halt if assertion detected
0 - halt
1
- restart
* - Bold font emphasizes default values.
EXAMPLE
Disable echo
>
set echo 0
OK
Change Aserver TCP port
>
set aserver port 12345
OK
Load defaults
>
set defaults
OK
Apply props visibility filter to status/control commands
>
set filter visi 1
OK, Boot Required!
Set RS232 Interface to 19200, 8 data bits, even parity, 1 stop bit