Commands Reference
CoolMaster PRM
27
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
COMPATIBILITY
CoolMaster 4000M
v 2.8.9
4.1.25 feed
SYNOPSIS
feed <UID> [±]<TEMPERATURE>
feed <UID> <XX.x>
DESCRIPTION
Provide indoor unit with ambient temperature measured by external device.
·
In feed <UID> [±]<TEMPERATURE> form:
<TEMPERATURE> parameter must be integer number. Command can work in relative or absolute
manner. If plus '+' or minus '-' sign precedes <TEMPERATURE> parameter it's value will be used as
requested delta. It means that ambient temperature will be increased (+) or decreased (-) by that delta.
Otherwise ambient temperature will be set to the given value.
·
In feed <UID> <XX.x> form:
Temperature parameter can be fractal number with 0.1 precision. In this case pre|- are not
supported.
For CoolMaster 4000M feed command is efficient only for Indoor units configured to take ambient
temperature from wall controller and not from internally measured return air temperature.
EXAMPLE
>feed 101 20
OK
Set unit 1-01 ambient temperature to 20ºC
>feed 101 -1
O K
Decrease unit 1-01 ambient temperature by 1ºC
>feed 101 +3
O K
Increase unit 1-01 ambient temperature by 3ºC
>feed 101 20.5
O K
Set unit 1-01 ambient temperature to 20.5ºC
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
Only CoolMaster 4000M
v 2.9.0