Commands Reference
CoolMaster PRM
18
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
·
PAC-YG66. CoolMaster 4000M v2.5.6
>stat 012
012 DIG IN:001111 OUT:000001 OK
OK
Position in String Example
Format
Description
0-2
012
NNN
PAC-YG66 Centralized Address
4-6
DIG
DIG
PAC-YG66 Identification
8-16
IN:001111
IN:XXXXXX
6 Digital inputs 1-6 status. X can be 0 or 1
18-27
OUT:0000001
OUT:XXXXXXX
6 Digital outputs 1-6 status. X can be 0 or 1
29-30
OK
OK or nnnn
OK or Failure code
·
PAC-YG63. CoolMaster 4000M v2.5.6
>stat 011
011 ANA 007.5 278.8 OK
OK
Position in String Example
Format
Description
0-2
011
NNN
PAC-YG63 Centralized Address
4-6
ANA
ANA
PAC-YG63 Identification
8-12
007.5
NNN.n
Analog input 1 value
13-17
278.8
NNN.n
Analog input 2 value
19-20
OK
OK or nnnn
OK or Failure code
4.1.16 stat2
SYNOPSIS
stat2 [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units. stat2 compared to stat1 has additional Filter Reset
Sign indication
EXAMPLE
>stat2
100 ON 12C 12,41C High Cool OK 0
101 OFF 32C 04,93C Low Dry OK 1
102 ON 07C 08,27C High Dry OK 0
103 OFF 01C 26,84C Med Dry OK 0
104 ON 04C 24,08C High Dry OK 0
105 OFF 11C 07,23C Low Dry OK 0
106 ON 11C 14,91C Auto Dry OK 0
107 ON 27C 12,94C Med Cool OK 1
OK
>stat2 101
101 OFF 32C 04,93C Low Dry OK 0
OK