GEMTEQ I/O 8. Maintenance and Fault Finding
Table 8-3
Configuration Error Codes
Code in F330 or F333
Condition
Comment
Numeric
Value (dec)
States
On
Fault
or
Warning
5
2 & 0
Fault
Table fault
The data tables declared in
the user program are read
only or are not large
enough to accommodate
the diagnostics data.
Modify user program.
9
3 & 0
Fault
Parameter fault
The configuration
parameter is out of range.
Modify user program.
17
4 & 0
Fault
Configuration timeout
A timeout has occurred
while trying to write new
configuration data to the
GEMCAN I/O Scanner
module.
If problem persists, replace
GEMCAN I/O Scanner
module and/or host
controller.
34
5 & 1
Warning
Input I/O data timeout
A timeout has occurred
while trying to read new
input data from the
GEMCAN I/O Scanner
module.
If problem persists, replace
GEMCAN I/O Scanner
module and/or host
controller.
66
6 & 1
Warning
Output I/O data timeout
A timeout has occurred
while trying to write new
output data to the
GEMCAN I/O Scanner
module.
If problem persists, replace
GEMCAN I/O Scanner
module and/or host
controller.
130
7 & 1
Warning
Statistics data timeout
A timeout has occurred
while trying to read new
statistics data from the
GEMCAN I/O Scanner
module.
If problem persists, replace
GEMCAN I/O Scanner
module and/or host
controller.
258
8 & 1
Warning
New output data timeout A timeout has occurred
while trying to inform the
GEMCAN I/O Scanner
module that new output
data is available.
If problem persists, replace
GEMCAN I/O Scanner
module and/or host
controller.
GEMTEQ I/O Technical Manual (T2031En)
Page 8-3
Rev.02 (10/10)
Summary of Contents for GEMTEQ I/O GEM80
Page 1: ...GEM80 GEMTEQ I O Series Controllers Publication No T2031En Rev 02 10 10 Technical Manual ...
Page 2: ...This page intentionally left blank ...
Page 28: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 8 Rev 02 10 10 ...
Page 30: ...GEMTEQ I O 3 GEM80 GEMCAN NETWORK GEMTEQ I O Technical Manual T2031En Page 3 10 Rev 02 10 10 ...
Page 44: ......
Page 102: ......