![Contrec 515 Operation Manual Download Page 41](http://html.mh-extra.com/html/contrec/515/515_operation-manual_2658179041.webp)
Instrument Calibration
515 HC04 - 8 June 2007
33
Parameters
↓
→
PARAMS
INPUTS OUTPUTS ALARMS COMMS TM/LOG SETUP TEST END
OPER
MODE
The operation mode allows an instrument to be configured for heating
and/or cooling applications.
•
HEAT
- Heating mode only calculates energy while feed
temperature is higher than return temperature.
•
COOL
- Cooling mode only calculates energy while feed
temperature is lower than return temperature.
•
BOTH
- Continues to calculate energy regardless of whether the
differential temperature is positive or negative.
Select the operation mode as required.
Press
or
to select one of the options.
METER
LOC
Enter the flowmeter location as being in either the feed or return line.
Press
or
to select FEED or RETURN.
PRESS
unit This parameter is available for viewing and editing only when the fluid
type is set to DEFAULT (water).
Enter the system absolute pressure used to provide greater accuracy of
calculations for high pressure applications.
TEMP-F
CORR
The feed temperature correction can be used for fine-tuning of
measurement. This parameter is added to the feed temperature and is
mainly used in cooling systems with RTD temperature sensors.
METER
TYPE
Enter the type of differential pressure flowmeter from the available list,
including those in accordance with ISO 5167.
Press
or
to select the type of meter as follows:
ISO-01 Orifice plate with corner tapping
ISO-07
Venturi tube ‘machined’
ISO-02 Orifice plate with D-D2 tapping
ISO-08
Venturi tube ‘welded’
ISO-03 Orifice plate with flange tapping
ISO-09
Venturi nozzle
ISO-04 Nozzle to ISA 1932
CONE-01 McCrometer: V-Cone
ISO-05 Nozzle ‘long radius’
CONE-02 McCrometer: Wafer-Cone
ISO-06 Venturi tube ‘as cast’
SET
Summary of Contents for 515
Page 4: ...iv 515 HC04 8 June 2007 ...
Page 8: ...viii 515 HC04 8 June 2007 ...
Page 16: ...Introduction 8 515 HC04 8 June 2007 ...
Page 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Page 80: ...Communications 72 515 HC04 8 June 2007 ...
Page 82: ...74 515 HC04 8 June 2007 ...
Page 88: ...80 515 HC04 8 June 2007 ...