Contemporary Controls BASrouter Portable Installation Manual Download Page 1

 

MS/TP Physical Layer  

BASrouter portable has two MS/TP port connections to its isolated EIA-485 
transceiver 

– a removable 3-pin connector and an RJ-11 jack. Either connector can 

be used for MS/TP line. The EIA-

485 transceiver’s + and – lines are tied to + and – 

pins of both connectors. The SC pin ties to the circuit ground of the EIA-485 
transceiver and is isolated from both the USB and Ethernet ports.  
You must connect the SC pin to the signal common of the MS/TP segment 

— or 

MS/TP communication will fail. 
 
 

3-pin (MS/TP) Pin Assignments 

RJ-11 (MS/TP) Pin Assignments 

    

   

 

 

 

 

 
 
 

Note: 

No end-of-line termination is provided on the BASrouter portable, giving it the 

ability to be inserted between any nodes of the MS/TP bus.

 

The BASrouter portable provides stand-alone routing between BACnet networks 
such as BACnet/IP, BACnet Ethernet, and BACnet MS/TP 

– thereby allowing the 

system integrator to mix BACnet network technologies within a single BACnet 
internetwork. The BASrouter portable is housed in a compact durable case. It 
connects to a 

PC or laptop computer’s USB port for power – 5 VDC using USB type 

B cable provided in the box. There are three physical communication ports on the 
BASrouter portable 

– a 10/100 Mbps Ethernet port with auto-negotiation and Auto-

MDIX using a shielded RJ-45 connector, an optically isolated EIA-485 port for MS/TP 
connection, and an RJ-11 port for an alternative MS/TP connection. Three LEDs 

– 

one each for power, Ethernet, and MS/TP receive-traffic provide visual indication of 
proper operation. DHCP client feature can be enabled for easy IP addressing and 
reduced network administration. Configuration is accomplished via BASrouter 
internal web page. MS/TP status web page provides diagnostic information about 
BACnet MS/TP bus. Routing status page provides a routing table of devices on the 
network. 

 

Electrical 

 

INPUT                               

USB type B

               

 

Voltage:                                 5 VDC            

 

Power:                                   1.5 W             
Current draw:                        300mA         

 

Environmental 

Operating temperature:     0°C to 60°C 
Storage temperature:        

–40°C to +85°C 

Relative humidity:             10

–95%, non-condensing 

Functional 

                Ethernet 

    MS/TP

 

 

Physical Layer:                 10BASE-T          EIA-485 

                                      100BASE-TX      RJ-11 

Cable length limit:             100 m                

1200 m

 

 

MS/TP data rate (bps):     9600, 19200, 38400, 76800 
MS/TP node limit:             254 devices total,  
                                         31 full-load devices per segment

 

Power Connection

 

The BASRTP-B is powered by a USB cable with Type B plug 

– cable is included in 

the box. It requires 5 VDC from the host computer, while drawing 300 mA of current. 
It can be powered from a USB hub, if desired. No driver installation is needed. 

 

 

Ethernet Port

 

The shielded RJ-45 connector used for Ethernet connection supports auto-
negotiation and Auto-MDIX. It automatically matches its duplex setting, flow control, 
data rate and signal polarity to whatever is supported by the attached equipment.  
Thus, the provided CAT5 cable is the only cable needed for the Ethernet connection. 

MS/TP Parameters 
MS/TP MAC address (Default Value = 00).

 This is the 8-bit (0

–127) MAC address of 

the router’s MS/TP port, in decimal. 

MS/TP Baud Rate (Default Value = 9600). 

The data rate of the MS/TP bus can be 

set to: 9600, 19200, 38400 or 76800 bps. All devices must use the same data rate. 

MS/TP Network (Default Value = 2001).

 This 16-bit decimal network number (1

65534) must be unique for all BACnet networks within the BACnet internetwork.  No 
other networks, regardless of type, can have the same network number. 

Max Masters (Default Value = 127). 

Only master nodes participate in the MS/TP 

token-passing process.  The highest master MAC address (in decimal) in the MS/TP 
bus is 127. You should use 127 if you are unsure of other MS/TP device addresses. 
 

BASrouter Portable  

 

 

 

 

 

 

 

 

 

 

 

 

 

BASRTP-B 

BACnet® Multi-Network Router 

 

 

 

 

 

 

 

 

  

     

Installation Guide

   

  

 

 

Installation

 

2   RT 

– 

4   SC 
5   RT + 

Reviews: