Contax VARTA BLOCK V Installation Download Page 1

VHB Industrial Batteries Ltd.

VHB Industrial Batteries Ltd.• 72 Devon Road, Unit 22, Brampton, Ontario L6T 5B4

Tel: (905) 790-0730 • 1-888-VHB-BATT • Fax: (905) 790-0744 • E-mail: [email protected]

04.04.01 0298 na

VARTA bloc V range
VbV 12121…VbV 4138

Application

Valve regulated VARTA bloc batteries (VbV) are maintenance
free lead-acid batteries.  The electrolyte is fixed as a gel.  They
have been designed for a long service life and for reserve
power supply systems with high safety requirements, space
saving installation and maintenance-free operation.  They can
be used universally both for capacitive discharge over a period
of hours and for short discharge periods of certain minutes.
They are used as reserve power supplies in power stations,
substations, information technology equipment, UPS systems,
for automation and traffic technology, and for emergency
power supply systems.

Construction

Positive Electrode

Rod plate with
VARTA-calcium-tin-alloy

Negative Electrode

Grid plate with calcium alloy

Separation

Micro-porous separator

Casing Material

Acrylonitrile-butadiene-styrene
(ABS), impact resistant,
optional: flame retardant
(FV 0)

Electrolyte

Dilute sulphuric acid
Fixed as a gel

Terminal Design

Leakproof safety pole rein-
forced with brass insert, M8

Connectors

Solid copper (20 x 3 mm),
insulated, bolt-on type

Cell Valve

Safety valve with flame arrestor

Charging

Float charge voltage:
2.23 volts/cell at 20

o

C

Temperature Range

-10

o

…+45

o

C

(Preferred value 20

o

C)

Installation

VARTA valve regulated lead-acid batteries are mounted on
insulated racks in upright position as a standard or built into
battery cabinets.  For space saving installation it is possible
to install them horizontally (plates must be in vertical position).
For use in earthquake zones special approved rack design is
available.  The safety provisions of the national and
international standards must be observed.

Features

 

4V / 6V / 12V bloc batteries

 

Maintenance-free operation

 throughout its service life

due to valve regulated construction.
The electrolyte is fixed as a gel.

 

Leakproof 

VARTA Safety Pole design

 

Long service life

 due to VARTA Rod Plate technology

in accordance with EUROBAT guide: 10+ years

 

Space-saving installation

 due to high energy and

power densities

 

Low ventilation requirement,

 using the reduction

factors

 

VARTA VbV batteries comply with the international
Standard IEC 896-2

Reviews: