67000171 Iss 09
I
NSTALLATION
Ensure the electricity supply is disconnected from any relevant fixed wiring before commencing the
installation. Ensure that the mains supply voltage is as stated on the rating label.
The supply circuit must be adequate for the input of the appliance.
I
MPORTANT
When installed in a bathroom the unit must not be connected via a plug and socket.
The heater must also be located in the appropriate zone of the bathroom, in accordance with section
601 of the Wiring Regulations (BS 7671).
The appliance should be fitted horizontally such that the cable entry is uppermost and the pullcord is at
the bottom.
The unit must be mounted a minimum of 1.8 metres from the floor, also a minimum of 150 mm below
ceiling level or any other projecting surface. It must also not be less than 350 mm from any adjacent
projecting surface.
The unit must not be located immediately below a fixed socket outlet.
Ensure that when in use the airstream is not obstructed by a cupboard or similar object.
WARNING
– DO
NOT
PLACE AEROSOLS OR SIMILAR CONTAINERS OR MATERIALS
SUSCEPTIBLE TO HEAT IN THE DIRECT AIRSTREAM.
C
ONNECTION TO THE
M
AIN
S
UPPLY
Electrical installation should be carried out by a competent installer, preferably registered with
NICEIC (National Inspection Council for Electrical Installation Contracting) in accordance with the 16
edition of the IEE Wiring Regulations, (BS.7671) and any relevant Local Authority Bye-Laws.
The heater is fitted with a 2-core mains supply cable and should be permanently connected to the
electricity supply via a double pole switch having 3 mm gap on each pole.
A switched Fused Connection unit to BS.1363 Part 4 is a recommended mains supply connection
accessory to ensure compliance with safety requirements applicable to fixed-wiring installation.
M
OUNTING
P
ROCEDURE
Using the mounting template supplied, position it horizontally a minimum of 1.8 m from floor to
underside and mark the position of the three fixing holes.
Drill and plug the wall suitable for No 8 screws.
Insert the two keyhole screws in wall leaving approximately 2 mm gap between head and wall.
Position the appliance on the partially inserted wall screws and secure the third wall screw
immediately above appliance.
C
ONTROLS
The BHM1 and BHM1T have a heat loading of 1 kW and the BHM2T has a heat loading of 2 kW.
The heater is controlled by a pullcord operated on/off switch. A neon indicator when lit shows that the
unit is operational.
The appliance is fitted with an Electronic Safety Control (ES). This is a safety device which switches
off the heater if for any reason the appliance overheats. The ES Control can only be re-set after the
appliance has cooled down. In order to re-set the ES Control proceed as follows:-
•
Switch off appliance by means of pullcord and leave for approximately 5 minutes.
•
Switch appliance back on and ES Control will re-set.
•
Ensure that the appliance is functioning correctly. If the ES Control operates again, the appliance
should be checked by a competent electrician.
T
HERMOSTAT
C
ONTROL
The BHM1T and BHM2T are fitted with a thermostat.
To set the thermostat to the required temperature, rotate the control knob to the highest setting (N
o
6).
When the desired room temperature is reached, rotate the control knob slowly in the opposite direction and
when the thermostat ‘clicks’ off, leave the control at this setting. Thereafter, the fan heater will control the
heat output automatically.
To set the heater to the Frost Watch mode, rotate the thermostat control knob fully to the lowest
setting (N
o
1). Thereafter the heater will trip in if the temperature drops sufficiently. The heater needs to
be in the ‘ON’ mode with the neon indicator light illuminated for this function to operate.
I
F
Y
OUR
H
EATER
D
OES
N
OT
W
ORK
•
Check re-set of E.S. Control as described under ‘controls’.
•
Check that the plug is firmly pushed into the wall socket with the socket switched ‘on’.
•
Check that the socket is live by using another appliance in it. (If it is not live, check the fuse at the
distribution board).
•
Check that the plug is wired correctly.
•
Check that the fuse has not blown at the flex outlet, in the plug or at the Distribution Board.
•
If you are replacing a fuse in the plug, a 13 Amp fuse approved by A.S.T.A to BS 1362 must be used.
•
Should none of the above remedies work, than disconnect heater from the mains and consult an
accredited service agent.
•
Do
NOT
attempt to repair the heater or unscrew the outer casing yourself.
•
If the appliance is still under guarantee, return it to your supplier.