Operating Instructions
Single-pole Conductor Rail System
SingleFlexLine Program 0815
BAL0815-0002g-US
www.conductix.us
translated document
page 20 of 128
3.3
Unsuitable environmental conditions
The conductor rail must
not be installed
and
not be operated
under these environmental conditions (see also Section 2.5, Section
2.8.4 and Section 3):
Direct UV radiation (direct sunlight).
In environments containing chemical substances or gases that can potentially permanently damage the conductor rail's materials
(corrosion) or drastically impact the insulation.
In ambient air that contains solvent vapors or aromatic compounds.
In ambient air that contains flammable or explosive gases or dusts.
In dusty environments.
Outdoors with free weathering.
In environments with relative humidity of more than 85 %.
In close proximity to splashing water.
In environments that require a higher protection class than IP 2X.
WARNING!
Faults due to incorrect operating conditions!
If the operating conditions change or are no longer within the specified range, the conductor rails
can malfunction due to short circuits, premature aging and damage to electrical and mechanical
components.
→
The conductor rail must be switched off if the operating conditions are no longer within the permis-
sible range described above.
→
The conductor rail must be switched off if it gets wet or is soiled. Clean or dry as specified.
→
Take the relevant measures to restore suitable operating conditions.