Operation Manual
Regulator
4 kW 560 V DC 40% Duty Cycle + 24 V DC
BAL9100-0126d-EN
www.conductix.com
original document
page 8 of 32
4.3
Protection Measures
The Regulator is protected against the following events:
•
Over voltage
Automatic shutdown if the voltage supplied by the Regulator exceeds 610 V.
Output protected up to 850 V (no reverse polarization)
•
Disconnected DC output
Automatic shutdown when unplugged/disconnected:
Protection against DC contact arcing; output voltage is removed.
Unplugging under load is not recommended
(proper wiring of the pilot pins: see chapter 7.4).
•
Over current
Output 1 is current limited
Automatic shutdown on strong overload or short circuit of output 1 - i.e. voltage < 100 V.
A high transient over current i.e. a sudden short circuit will damage the device.
•
Reverse current
Output 1 is protected against reverse current flow -
but not protected against reversed polarization i.e. reverse battery connection.
•
Over temperature
Automatic shutdown on internal over temperature
i.e. as a consequence if maximum rated temperature and/or maximum continuous
output power are exceeded.
•
Repetitive shutdowns
Shutdown procedures (i.e. turning off the Regulator through the interface plug)
discharge the energy stored inside the Regulator. To avoid overheating, the number of
shutdown procedures is limited to 3 within 30 seconds. This number exceeded, the
Regulator will remain in disable mode and respond only passed a delay of 30 seconds.
4.4
Mechanical Integration
•
Dimensions
See drawing
Versions 91012-411-3090871 and 91012-411-3090872 are mechanically identical.
•
Weight
10 kg (without cables or Pickup)
•
Surface temperatures
Heatsink surface temperature may reach up to 70°C depending on operating conditions
To a lesser extent the housing may also get hot.