background image

Page 1 of 2 

 

 

 

 

Montageanweisung  
Operating Instructions 
Instrucciones de Montaje 
Instructions de Montage 
Instruzioni d’impiego 

 

 

MDR 5 / MDR 5-K

Druckschalter / Pressure switch

 
 

The relevant standards for running and installing electrical appliances are to be observed. 
Installation and connection by skilled personnel only, after installing accessories function 
of device to be checked by skilled personnel only. 

 

 

2 ~ 

 

 

3 ~ 

 

 

 

 

 

 

 

EN/IEC 60947 - 4 - 1 (AC-3) 

 

I

q

 

 

I

the

 

Typ “2“ 

 

NH00 / gL 

 

U

N

 

(50/60 Hz) 

3 kA 

25 A 

50 A 

500 V~ 

 

CAUTION: Pressure setting is only possible when applying 
                  pressure to the switch 

 

Cut-out pressure p

o

 

 

Differential 

Δ

Δ

p = 

p

o – 

p

 

Press wheel downwards

 

 

 

 

 

 
 
 
 
 

 

 

 

If the spindle moves when turning, lowest 
possible 

Δ

p

 has been reached. In order to 

loosen, turn wheel to the left holding the 
spindle tight. 

IP 54 

p

o

 lower: 

turn wheel 
to the left 

p

o

 higher: 

turn wheel 
to the right 

Δ

p

 lower: 

turn wheel 
to the right 

Δ

p

 higher: 

turn wheel 
to the left

 

Spindle 

Summary of Contents for MDR 5-K

Page 1: ...vice to be checked by skilled personnel only 2 3 EN IEC 60947 4 1 AC 3 Iq Ithe Typ 2 NH00 gL UN 50 60 Hz 3 kA 25 A 50 A 500 V CAUTION Pressure setting is only possible when applying pressure to the switch Cut out pressure po Differential Δp Δp po pu Press wheel downwards If the spindle moves when turning lowest possible Δp has been reached In order to loosen turn wheel to the left holding the spin...

Page 2: ...ssure Control GmbH Warendorfer Straße 47 51 D 59320 Ennigerloh Telefon 49 0 25 87 89 0 Telefax 49 0 25 87 89 140 info condor cpc com www condor cpc com 3 2 max cut in pressure 1 8 min cut in pressure Setting range off the cut in pressure Example Cut out pressure po 4 bar Cut in pressure pu between 1 8 and 3 2 bar possible ...

Page 3: ...elektrischer Anlagen gültigen Vorschriften Einbau und Anschluss nur durch Fachkraft nach Anbringung von Zubehör Funktionsüberprüfung durch Elektrofachkraft erforderlich The relevant standards for running and installing electrical appliances are to be observed Installation and connection by skilled personnel only after installing accessories function of device to be checked by skilled personnel onl...

Page 4: ...R5 10 3 6 1 10 3 A 500 V 50 A R5 14 9 0 14 0 A 500 V 63 A R5 18 11 0 18 0 A 500 V 50 A Auslösekennlinie R5 Tripping curves R5 R5 0 86 7 0 A R5 6 1 18 A t y IN x y t y 5 C 0 85 5 C 0 82 20 C 1 00 20 C 1 00 40 C 1 12 40 C 1 12 02 11 2005 Condor Pressure Control GmbH Warendorfer Straße 47 51 D 59320 Ennigerloh Telefon 49 0 25 87 89 0 Telefax 49 0 25 87 89 140 info condor cpc com www condor cpc com ...