30
Operator Interface
2583701_C_EN_1812_Nortec-GS_OM
Nortec GS
RH Alerts Tab
Note:
is set to "RH P" or "RH PI".
–
RH Alerts:
allows you to enable or disable the alert function that
warns if sensed humidity is too high or too low.
Options:
On
– enables the function.
Off
– disables the function.
Factory setting:
Off
Note:
The following settings are only available if the RH Alerts func
-
tion is enabled.
–
RH High:
allows you to set the upper limit value of the humidity
sensor signal. The RH High warning message is triggered when the
signal value exceeds this limit.
Setting range:
20-95%
Factory setting:
75%
–
RH Low:
allows you to set the lower limit value of the humidity
sensor signal. The RH Low warning message is triggered when the
signal value drops below this limit.
Setting range:
20-95%
Factory setting:
20%
–
Sensor Min:
allows you to set the minimum signal value of the
humidity sensor. If the signal value drops below this setting, the
sensor is assumed to be damaged or disconnected. The RH Signal
warning message is triggered when the signal value drops below
this limit, and humidification stops.
Setting range:
1-10%
Factory setting:
5%