11.0
TECHNICIAN MENU
The service menu has settings that assist the installation and maintaining process. Each setting
is defined as shown below.
Table 11 - Technician menu
Icon
Description
Alm Setup
Alarm sensor setup for temperature, humidity, smoke, no air flow, etc.
Analog Offsets
Sensor calibration offset
Dig In Setup
Controller digital input setup
Network
CLAN network setup
Manual Control
Manual control for each components
Table 12 - Technician menu description
11.1
Alarm Setup
The controller supports a general alarm or global alarm for the following events. Each individual
alarm can be configured to be part of a global arm. R2 is the second relay which is connected to a
normally opened dry contactor. Consult the electrical wiring diagram for more information.
Figure 35 - Alarm setup
R2 = Selectable alarms
Figure 36 - Alarm Setup
Note: S.W for switching over option only shows up when more than one controllers are
connected for cLAN configuration.