CONDENSATE DRAIN

 

 

Evaporator and the condensing sections (air cooled only) are provided with individual condensate drains, 3/4" 
stub.  Hook both drains with "P" traps.  Provide 1/4" slope per 10 feet. 

 

         

 

CAUTION:

 

Drain line contains boiling water from humidifier. Use copper or other  

Suitable material for the drain.   

 
NOTE: COMPU-AIRE HIGHLY RECOMMENDES AN AUXILIARY DRAIN PAN TO BE 
PROVIDED UNDER THE UNIT. (TO BE FIELD FURNISHED AND INSTALLED BY OTHERS)  

 

AIR FLOW 

 

The evaporator and the condensing sections are provided with variable pitch motor pulley which are field 
adjustable.  Refer to the specification data for the air flow data.  In case field adjustments are made, check to 
verify the motor full load amps. 