TECP-91-005 • Issue 5 • October 2017
Page 16
© 2017
CommScope
. All Rights Reserved.
Figure 16. Grounding the Panel
2. Using AWG 14 (1.6mm) solid copper wire, secure a crimp lug to one end of the
ground wire (installer provided). Secure the crimp lug to panel with two M4
screws. Torque the screws to approximately 15 pound-inches (1.7 Newton
meters).
3. Connect the other end of the ground wire to the earth ground conductor. Ensure
this connection is made using methods and hardware that meets all applicable
local and national electrical codes.
Caution: Reliable earthing of rack-mounted equipment should be maintained.
Particular attention should be given to supply connections other than direct
connections to the branch circuit.
26275-A
2RU CHASSIS
1RU CHASSIS
2-HOLE LUG
SECURE
TO OFFICE
GROUND
SECURE
TO CHASSIS
PEM NUTS