Figure 9. RJ45 Connector Wiring
When bringing Ethernet cable into the panel, make sure that cable is run vertically along the left
or right side of the bay. Route Ethernet Cable to the rear of the panel. Secure cable to panel
using tie points provided. Leave enough cable slack to make connection to the appropriate
location on the Controller.
Note:
All Ethernet or PoE cabling should be routed away from any sharp edges and
properly secured in place to prevent chafing and to provide strain relief. This may be
achieved by tie-wrapping the wires to the rack frame or by a similar means.
3.9
Connecting the Panel to the Quareo Network
After the Quareo HDEP has been physically installed on the rack, a software procedure must be
performed to access the panel controller and make the controller known on the Quareo network.
This procedure is done using a web browser to access the configuration web pages of the panel
controller. This can be done at the panel by connecting an ethernet cable from a computer to the
RJ-45 port of panel controller to gain network access to the controller. Once the IP address of
the panel is known, the user can input the address of the panel controller into the web browser to
access the configuration pages.
Instructions for performing the software procedure described above can be found in TECP-90-
805, which is available on the CommScope website.
4
INSTALLING MODULES AND IFC CABLES
Note:
Remove the dust cap, inspect, and clean MPO connector per ADCP-96-150
instructions before terminating. Remove the ferrule dust cap from one of the patch cord
connectors and then clean the connector as specified in the Optical Fiber Connector Wet
and Dry Cleaning Instructions (ADCP-90-159) or by locally approved procedures.
Modules available for use in the Quareo 1RU high density panel include the following:
• LC-LC adapter pack
• MPO-MPO adapter pack
• LC-MPO module
• LC cabled module