507735-03
Page 16 of 53
Issue 1933
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 − 10,000 ft.
Number
of 90
°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
045
070
090
110
1
20
15
n/a
n/a
61
46
24
n/a
100
80
43
n/a
127
127
108
108
2
15
10
56
41
19
95
75
38
122
122
103
103
3
10
n/a
51
36
14
90
70
33
117
117
98
98
4
n/a
46
31
n/a
85
65
28
112
112
93
93
5
41
26
80
60
23
107
107
88
88
6
36
21
75
55
18
102
102
83
83
7
31
16
70
50
13
97
97
78
78
8
26
11
65
45
n/a
92
92
73
73
9
21
n/a
60
40
87
87
68
68
10
16
55
35
82
82
63
63
Concentric Termination Elevation 0 − 10,000 ft.
Number
of 90
°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
045
070
090
110
1
15
10
n/a
n/a
53
38
22
n/a
90
70
39
n/a
111
111
104
104
2
10
n/a
48
33
17
85
65
34
106
106
99
99
3
n/a
43
28
12
80
60
29
101
101
94
94
4
38
23
n/a
75
55
24
96
96
89
89
5
33
18
70
50
19
91
91
84
84
6
28
13
65
45
14
86
86
79
79
7
23
n/a
60
40
n/a
81
81
74
74
8
18
55
35
76
76
69
69
9
13
50
30
71
71
64
64
10
n/a
45
25
66
66
59
59
* Size intake and exhaust pipe length separately. Values in table are for intake or exhaust, not combined total. Both intake and
exhaust must be same pipe size.
Table 7.
Summary of Contents for Century GDD95C Series
Page 30: ...507735 03 Page 30 of 53 Issue 1933 Figure 50 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 36: ...507735 03 Page 36 of 53 Issue 1933 045B3 070B4 090C4 110C5 Figure 57 Typical Wiring Diagram ...
Page 48: ...507735 03 Page 48 of 53 Issue 1933 Troubleshooting Heating Sequence of Operation ...
Page 49: ...507735 03 Page 49 of 53 Issue 1933 Troubleshooting Heating Sequence of Operation continued ...
Page 50: ...507735 03 Page 50 of 53 Issue 1933 Troubleshooting Cooling Sequence of Operation ...
Page 51: ...507735 03 Page 51 of 53 Issue 1933 Troubleshooting Continuous Fan Sequence of Operation ...