IE-LGR-UxxxxM-23
35
set to not require the PIN code. If the PIN code is set on the SIM card
and the required pin is set incorrectly in the device configuration,
the SIM card will be blocked when attempting to connect to the mobile
operator network, see
chapter. This option does
NOT change the PIN code settings on the SIM card, only the PIN code
required for the SIM card is entered here.
Modem
– Text message - General
____________________
In the case that the alarm condition persists for a longer time,
determine whether the warning text message should be sent on the
alarm inception only, or whether it should be repeated. The repetition
interval can be pre-set in a range of 30 minutes to 24 hours.
Specify the total daily limit for the number of SMS messages sent from
the device (i.e. the maximum number of sent SMS messages per day
for both battery and external power together) and the maximum daily
limit for the number of messages sent in battery mode (to conserve
battery capacity). Before sending a message, the daily limit value will
be ascertained. Should the limit value be reached, the respective
recipient will receive a message indicating that the daily limit
of the outgoing messages has been reached. For the day in question
no further messages will be sent to the recipient’s number. When it is
required to send the message to another recipient, only a notification
is sent about the daily message limit error. No further messages will be
sent out to this recipient’s number on this day. The daily limit will be
reset at time 00:00.
If you want alarm text messages to be sent, remember to assign
the pertinent recipients of these messages to the particular alarms.
This concerns alarms on measurement channels, system alarms,
as well as warnings about exceeding the data memory occupancy limit.
This assignment is to be performed during setting the individual alarms.
Modem
– Text message - Recipients
__________________
In this panel you can set the recipients of the SMS messages. You may
enter up to 4 recipients of text messages that the device will work with.
Each recipient is identified by their name, telephone number, additional
text and an activity flag.
If you clear this flag, text messages will not be
sent to the selected user, but all its settings will remain unchanged.
This way you can easily deactivate a user in a simple manner
and restore it later.
Modem
– Text message - Keep alive SMS
______________
In this panel you can set Keep-alive SMS sending parameters.
It means sending information messages
at regular intervals
,
regardless of alarm status.
Summary of Contents for U0110G
Page 5: ...IE LGR UxxxxM 23 5 Dataloggers UxxxxM and UxxxxG U0141M U0141G models...
Page 61: ...IE LGR UxxxxM 23 61 Dimensions U0110M U0110G U8410M U8410G U0121M U0121G...
Page 62: ...62 IE LGR UxxxxM 23 U0141M U0141G U3120M U3120G U4440M U4440G...
Page 63: ...IE LGR UxxxxM 23 63 U3121M U3121G U3631M U3631G...
Page 64: ...64 IE LGR UxxxxM 23 U0141TM U0141TG U0843M U0843G U5841M U5841G U6841M U6841G U7841M U7841G...