 transmitters Web Sensor T554x and T654x 

 

 

 

with Ethernet connection                                                                                           

 

 

PRODUCT DESCRIPTION   

 

CO

2

 transmitters Web Sensor T554x and T654x with Ethernet connection are designed for measurement of temperature and relative 

humidity of air and for measurement of CO

2

 concentration in air. Transmitters can be used in a chemically non-aggressive environment. 

 

The CO

2

 concentration is measured using the dual wavelength NDIR sensor with the multipoint calibration. This principle compensates 

aging of the sensing elements and offers maintenance free operation and outstanding long term stability. 

 

Relative humidity transmitters allows to determine other calculated  humidity variables like dew point temperature, absolute humidity, 
specific humidity, mixing ratio and specific enthalpy

 

Measured and calculated values are displayed on a two-line LCD display or can be read and then processed via Ethernet interface. The 
device  is  also  equipped  with  three-color  LED  for  visual  indication  of  the  CO

2

  concentration.  The  following  formats  of  Ethernet 

communication are supported: www pages with user-design possibility, Modbus TCP protocol, SNMPv1 protocol, SOAP protocol and XML. 

The transmitter may send also a warning message if the measured value exceeds adjusted limit. The messages can be sent up to 3 e-
mail addresses or to Syslog server and can be sent by SNMP Trap too. The alarm states are also displayed on the websites. The device 

setup can be made by the TSensor software (see 

www.cometsystem.com

) or using the www interface. 

 

type * 

measured values    

construction 

mounting 

 

 

 

 

T5540 

CO

2

 

ambient air 

wall 

T6540 

T + RH + CO

2

 + CV 

ambient air  

wall  

T5541 

CO

2

 

probe on cable 

wall  

T6541 

T + RH + CO

2

 + CV 

probes on cable 

wall 

T5545 

CO

2

 

duct mount 

fix by means of the cable gland  

 

*  models marked TxxxxZ are custom - specified devices 

                   T…temperature,  RH…relative humidity,  CO

2

…concentration CO

2

 in air,  CV…computed values   

 

 

INSTALATION AND OPERATION

 

 

The transmitters T5540 (T6540) and T5541 (T6541) fasten on a flat surface with two screws or bolts. The external CO

2

 probe unpack and 

connect to the T5541 (T6541) device. Place the external probes into the measured area. The T5545 transmitter install by inserting the 
metal stem into the Pg21 cable gland so that the measured air was fed into the head of device (see Technical specification). To fasten the 
stem it is also possible to use the flange PP4 (optional accessory).  Pay attention to the location of the device and probes. Incorrect choice 

of working position could adversely affect accuracy and long-term stability of measured value. Devices don’t require special maintenance. 
We recommend you periodical calibration for validation of measurement accuracy.

  

 

DEVICE SETUP

 

 

For network device connection it is necessary to know new suitable IP address. The device can obtain this address automatically from a 

DHCP server or you can use the static IP address, which you can get from your network administrator. Install the latest version of TSensor  
software to your PC and according to the “Device connection procedure” (see next page) you connect the Ethernet cable and power supply 
adapter. Then you run TSensor program, set the new IP address, configure the device in accordance with your requirements (alarm 

conditions, limits of CO

2

 LED indication, sending of e-mail) and finally store the settings. The device setup can be made by the web 

interface too (see manual for devices at 

www.cometsystem.com

 ).  

 

After device switching on starts internal test. During this time (about 20 s) LCD display shows  ----  instead value of CO

2

 concentration. 

The IP address of each device is set by the manufacturer to 192.168.1.213

 

ERROR STATES 

 

Device continuously checks its state during operation and if an error appears, it is displayed relevant code: Err 1 - measured value (except 
of  CO

concentration)  or  calculated  value  is  over  the  upper  limit,  Err 2  -  measured  or  calculated  value  is  below  the  lower  limit  or 

concentration CO

2

 measurement error occurred, Err 0, Err 3 and Err 4 - it is a serious error, please contact distributor of the device. 

 

SAFETY INSTRUCTIONS  

 

 

-   Don´t use and don’t store the devices without the cover of the temperature and humidity sensors.  
-  Temperature and humidity sensors have not to be exposed to direct contact with water and other liquids. 

-   It is not recommended to use the humidity transmitters for long time under condensation conditions. 
-   Take care when unscrewing the filter cap as the sensor element could be damaged. 
-  Use only the power adapter according to technical specifications and approved according to relevant standards. 

-   Don’t connect or disconnect transmitters while power supply voltage is on.   
-   Installation, electrical connection and commissioning should be performed by qualified personnel only. 

-   Devices contain electronic components, it needs to liquidate them according to legal requirements. 
-   To complement the information in this data sheet read the manuals and other documentations that are 

available in the Download section for a particular device at 

www.cometsystem.cz

.  