Comet T4111 Instruction Manual Download Page 4

 

  IE-SNC-T4111-06 

LCD Info mode 

Several settings of installed transducer is possible to verify without a use of the computer. It is 

necessary to connect at least power of current loop I1. 

Unscrew  the  transducer  lid  and  shortly  press  button  between  display  and  interconnection 

terminals by means of a tool (e.g. screwdriver). 

 

Range  and  type  of  value  for  output  1  (current  loop  I1  =  symbol  „1“on 
display). Type of value, assigned to output 1, is indicated by displayed unit 
(here  °C).  Upper  line  displays  current  value  corresponding  to  measured 
value (lower line). Here 4 mA corresponds to -30 °C. 

 

 
Press  button  again  to  get  value  for  upper  point  (same  output,  same  value) 
similarly as at previous point. Here 20 mA corresponds to 80 °C. 
Press button again to end info mode and display actual measured values. 

 

Notice:

 during info mode no measurement and no output current generation 

proceed. The transducer stays at info mode 15 s, then automatically goes back to measuring cycle. 
 
 

Readings on LCD display 

°C, °F 

Reading next to this symbol is measured temperature or error state of value. 
 
 
 

Technical parameters: 

 

Analog output: 

 

 

Current loop with range from 4 to 20 mA 
Current output in case of error: <3.8 mA or >24 mA 

 

Measuring parameters: 

Temperature probe: Pt1000/3850 ppm connected by shielded cable of maximum 

length 10m 

Measuring temperature range: -200 to +600 °C (can be limited by applied 

temperature probe model) 

Resolution: 0.1 °C 
Accuracy without probe: current output ± (0,15 + 0,1% FS) °C, ±0,2 °C for value on 

LCD display  

 

Recommended interval of calibration: 2 years 
Measuring interval and LCD display refresh: 0.5 s 
Communication with computer: via USB port by means of USB communication  

cable SP003 

Power: 9 to 30 V dc, maximum ripple 0.5 % 
Protection:  IP65 
 
 
 