Comet T4111 Instruction Manual Download Page 2

 

  IE-SNC-T4111-06 

Instruction manual for use of T4111 transducer 

Transducer  is  designed  for  temperature  measurement  at  °C  or  °F  by  means  of  an external 

temperature  probe  with  Pt1000  sensor.  Measured  temperature  is  converted  to  linearized  unified 
signal  4-20  mA.  Measured  values  are  displayed  on  LCD  display.  It  is  possible  to  switch  OFF 
the LCD at all. Current loop has two-wire connection and requires power from evaluation device.  

All  transducer  setting  is  performed  by  means  of  the  PC  connected  via  the  optional  SP003 

communication cable (not included in delivery). Program 

Tsensor

 for transducer setting is available 

to  download  free  at 

www.cometsystem.com

.  Program  enables  to  assign  temperature  measuring 

range.  It  supports  make  the  adjustment  of  the  device  too.  This  procedure  is  described  at  file 

Calibration manual.pdf

“ which is installed commonly with the software. 

Transducer  version  T

xxxx

L

  with  watertight  male  connector  instead  of  a  cable  gland  is 

designed  for  easy  connection/disconnection  of  the  output  cable.  The  protection  of  male  Lumberg 
connector RSFM4 is IP67. 

Models  marked  T

xxxx

Z

  are  non-standard  versions  of  the  transducers.  Description  is  not 

included in this manual. 

Please read instruction manual before the first device connection.

 

Device setting from the manufacturer 

Transducer is set from the manufacturer to the following parameters: 

value at output I1:

 4 – 20 mA corresponds -200 to +600 °C 

display:

 switched ON 

 

Modification of the setting is possible to do by means of the PC using procedure described 

at the end of this document. 

Installation of the transducer 

Transducer  is  designed  for  wall  mounting.  There  are  two  mounting  holes  at  the  sides  of 

the case.  Interconnection  terminals  of  T4111  are  accessible  after  unscrewing  four  screws 
and removing the lid. Lace the cable through a gland at the case wall. Connect the cable to terminals 
with respecting the signal polarity (see figure). Terminals are self-clamping and can be opened by 
a suitable screwdriver. For the opening, insert the screwdriver to upper terminal hole and lever by 
him. Do not remember to tighten glands and case lid with inserted packing after cables connecting. 
It  is  necessary  for  warranting  of  protection  IP65.  Connect  complementary  female  connector 
for T4111L transmitter in accordance with the table in Appendix A of this manual. 

It  is  recommended  to  use  shielded  twisted  copper  cable,  maximal  length  1200m.  The  cable 

must be located at indoor rooms. The cable should not be led in parallel along power cabling. Safety 
distance is up to 0.5 m, otherwise undesirable induction of interference signals can appear. Outside 
diameter of the cable for T4111 device must be from 3,5 to 8 mm (e.g. SYKFY), for device T4111L 
with respect to the female connector. Do NOT connect shielding at connector side. 

External temperature probe should be of „shielded two-wire“ type. For leading of the cable 

same  recommendations  are  valid  as  for  current  loop  cable,  i.e.  cable  should  be  located  as  far 
as possible  from  potential  interference  sources.  Maximum  probe  cable  length  is  10  m.  Connect 
probe  cable  shielding  to  proper  terminal  and  do  not  connect  it  to  any  other  circuitry  and  do  not 
ground it. If connected probe is equipped with metal stem, we recommend using probes with metal 
stem not connected to cable shielding. Or else it is necessary to arrange metal stem is not connected 
to any other circuitry. 

Electrical  system  (wiring)  may  do  only  worker  with  required  qualification  by  rules 

in operation. 