Web Sensor P8552 with binary inputs 

PoE Web Sensor P8652 with binary inputs                                                                                          

 

 

PRODUCT DESCRIPTION   

 

Web Sensor P8552 and Web Sensor P8652 

with Ethernet connection

 

are designed to measure temperature and relative humidity of the 

air. The devices are equipped with two connectors for connection of the temperature and humidity external probes and three binary inputs 
for two-states signals. The dry contact or two-state voltage signal can be connect to the binary input. The devices are powered from an 
external power supply adapter. Web Sensor P8652 supports also Power over Ethernet (PoE). 

 

Measured values

 can be read and then processed using an Ethernet connection. The following formats of Ethernet communication are 

supported: www pages with user-design possibility, Modbus TCP protocol, SNMPv1 protocol, SOAP protocol and XML. The instrument 
may send  also a warning message if the measured value exceeds adjusted limit. The messages can be sent up to 3 e-mail addresses or 

to Syslog server and can be sent by SNMP Trap too. The alarm states are also displayed on the websites. The device setup can be made 
by the 

TSensor

 software (see 

www.cometsystem.com

and using the www interface. 

 

type * 

measured value  

 

design 

 

 

 

 

 

 

mounting   

PoE 

 

 

P8552    

temperature, humidity 

2-chanel transducer for external probe using, three binary inputs 

wall 

 

no  

P8652 

temperature, humidity 

2-chanel transducer for external probe using, three binary inputs 

wall 

 

yes 

 

 

*  models marked Pxxxx

Z

 are custom - specified devices

 

 

INSTALLATION AND OPERATION 

 

The devices are designed for wall mounting with two screws or bolts. Pay attention to the location of the device and probe. Incorrect choice 

of working position could adversely affect accuracy and long-term stability of measured values. The Web Sensor with attached DSRH/C 
or DST/C probe install always vertically with the sensor cover downwards. Devices don´t require any special operation and maintenance. 
We recommend you periodic calibration for measurement accuracy validation.

  

 

DEVICE SETUP 

 

Contact your network administrator to obtain necessary information for the device connection into the network (IP address, default gateway, 
subnet mask) and check if there is no IP address conflict when you connect the device into network for the first time. IP address of each 

device is set by manufacturer to 

192.168.1.213

. Install the latest version of TSensor to your PC, connect the Ethernet cable and connect 

the power supply (see “Device connection procedure” on the other side of this data sheet). 

 

Run the configuration software 

TSensor

. Set the „

Ethernet“

 

communication interface and press „

Find Device

 

button. According to MAC 

address (see device label) select device for configuration and by „

Change IP Address

 

button set new address according to network 

administrator instructions. Gateway IP address may not be entered if you want to use the device only in local network.

 

After changing of 

IP address the device is restarted and new IP address is assigned. Restart of the device takes about 10 seconds. 

 

The device setup can be made by the web interface. Main page will be shown when you insert device address 
into address bar of your web browser. Access to device setup is possible via tile 

Settings

 (see user manual). 

 

To restore the Web Sensor to the 

factory default settings

 use the button inside the device. 

Turn of the power supply and press the button (see picture). Turn on the power supply and keep 
the button pressed for 10 sec. 

 

ERROR STATES AND TROUBLESHOOTING

 

 

Device continuously checks its state during operation and if an error appears, the device sends the error message. The detailed description 

of the error messages is given in the user manual Chapter “Troubleshooting”. 

 

SAFETY INSTRUCTIONS  

-   Don’t  use and don’t store the external relative humidity probe without a sensor cover. 
-   It is not recommended to use the external relative humidity probe for long time under condensation conditions.

 

-   Don’t connect or disconnect thermometers  while power supply is on. 
-  Installation, electrical connection and commissioning should be performed by qualified personnel only. 

-  Use the power adapter according to technical specifications and approved according to relevant standards only.

 

-  The external probe cable should be located as far as possible from potential interference sources. 
-  If it is necessary connect the device to the Internet, properly configured firewall must be used.  

The device should not be used for applications, where malfunction could cause to injury or damage to property. 

-   Devices contain electronic components, it needs to liquidate them according to legal requirements. 
-  

To supplement the information

 provided in this data sheet, use the manuals and other documentations which 

are available at 

www.cometsystem.com 