Comelit 43CPC016EN Installation And Operation Manual Download Page 1

ERACLE 16

43CPC016EN

CONVENTIONAL FIRE ALARM 

CONTROL PANEL 

WITH 8 TO 16 ZONES

INSTALLATION AND 

OPERATION MANUAL

Summary of Contents for 43CPC016EN

Page 1: ...ERACLE 16 43CPC016EN CONVENTIONAL FIRE ALARM CONTROL PANEL WITH 8 TO 16 ZONES INSTALLATION AND OPERATION MANUAL...

Page 2: ...Module 43ECR032 13 4 2 Repeater Panel 15 4 3 Class Change Mode 16 4 4 Connecting the Zone and Sounder Circuits 16 5 SYSTEM PROGRAMMING 5 1 Sounder Delay 18 5 2 Double Action Mode 19 5 3 Instant Action...

Page 3: ...in fire detection and fire alarm systems in and around buildings Essential Characteristics Performance Performance under fire conditions Pass Response delay response time to fire Pass Operational rel...

Page 4: ...with consumption 200 at a normal mode Unlimited number of manual call points Thresholds for zone conditions 0 2 mA Open circuit fault condition 2 10 mA Normal condition 10 110 mA Fire alarm condition...

Page 5: ...93 non condensing 2 2 General Technical Specifications of Relay Module 43ECR032 Number of relays 8 Power supply 24V Current consumption in normal condition 8mA Additional current consumption for ever...

Page 6: ...m the spare parts kit on page 31 Perform an exposed or flush mounting see items 3 1 and 3 2 Run all external cables into the box to establish connection but do not connect them at this stage yet Run t...

Page 7: ...ion 20 page 31 of the fire alarm panel on 25 mm thick drywall Use the dimension shown in Figure 6 to draw and cut out the mounting openings in the drywall Attach the hangers to the internal side of th...

Page 8: ...ngers and the bolts supporting the metal box 3 3 Configuration of the Basic Modules Figure 9 1 Metal clamp for supporting the battery 2 Clamp for supporting the main power supply cable 3 Terminal for...

Page 9: ...R 10K from the supplied spare parts kit position 1 page 31 to the sounder terminals DOUBLE Double Action Mode see item 5 2 MASTER Master Panel Mode see item 5 4 SLAVE Repeater Panel Mode see item 5 5...

Page 10: ...It is possible that the battery might not be charged at the panel initial start up In this case the BATT LOW LOST at the control module and the GENERAL FAULT at the front panel will light on until the...

Page 11: ...ication Connecting of Additional 4 Zone Expander 1 Connect the connectors of the expanders 2 Fix the second 4 zone expander with screws from the spare parts kit position 10 page 31 to the metal box fr...

Page 12: ...sly and Sounders 2 4 of the expander will be pulse activated 2 sec sound 2 sec silent The method of adding of 4 sounder expander is analogical to that of adding a 4 zone expander module see Figure 14...

Page 13: ...ormally close the contact Figure 17 Special jumper J1 when this jumper is set the first zone relay is activated by the module relays after the button SILENCE ALARM see item 6 2 on the control panel is...

Page 14: ...r configuration of 43ECR032 Figure 18 Connecting between one Relay Module and Master Panel Figure19 Connecting between two Relay Modules and Master Panel Master Panel ERACLE 16 Master Panel ERACLE 16...

Page 15: ...e connection between the Master and Slave ERACLE 16 panels Connecting of Repeater Panel When adding a repeater panel in the fire system Turn off the main and the stand by power supplies Connect the re...

Page 16: ...the main electric network Turn on the main power supply In normal operation mode only the POWER SUPPLY 230V LED lights up on the front panel of the fire alarm station NOTE In case other indicators ar...

Page 17: ...front panel the problem lies with the connection of the circuits in these zones Check the polarity of the connection of the devices and whether there is a detector removed from its base Activate one...

Page 18: ...SYSTEM PROGRAMMING 5 1 Sounder Delay This is an option for setting a delay on the Sounders activation when the panel enters Fire mode The indication on the front panel the FIRE LED however will light...

Page 19: ...l not activate the sounders and the signalization on the front panel because during time interval 2 no second alarm signal is generated EXAMPLE 2 In this case the fire panel will activate the sounders...

Page 20: ...in item 4 1 and the connection between the Master Panel and the Slave in item 4 2 5 5 Repeater Panel Mode In order to program the Repeater Panel mode Set a jumper on the Slave position of the main pan...

Page 21: ...expanders the LEDs of zones programmed in Instant Action mode i e with a set jumper light up in orange and all the rest in red On the 4 sounder expanders the Fault LED SND1 SND4 4 The following LEDs l...

Page 22: ...ights permanently at disabled sounders Blinks at trouble in the sounder circuit OUTPUT DELAY yellow Lights permanently at programmed outputs time de lay a jumper is set on the TIME DELAY terminal ENAB...

Page 23: ...ond if ZONE 1 is enabled and lights permanently if ZONE 1 is disabled Press TEST SCROLL button until you reach the zone which has to be disabled The respective zone LED blinks in yellow 2 blinks per s...

Page 24: ...the sounder disabling mode also by pressing the TEST SCROLL button as in that case the procedure for initial start up will not run To enable the sounders Press ENABLE DISABLE button DISABLE ENABLE LE...

Page 25: ...EST SCROLL button to continue with the system testing TEST LED will continue blinking The ZONE 1 LED lights out the zone is not longer in test mode The ZONE 2 LED blinks in yellow 2 blinks per second...

Page 26: ...ULT RP LED No connection with the Repeater panel Repeater fault GENERAL FAULT AUX LED Auxiliary supply fault GENERAL FAULT EARTH LED Short circuit to earth GENERAL FAULT uPFAULT LED Processor fault It...

Page 27: ...ti vated It is disabled by press ing the SILENCE BUZZER button FAULT A FAULT relay is activated The GENERAL FAULT yellow LED and the fault LED according to the Ta ble in item 7 1 light up simultaneous...

Page 28: ...28 ERACLE 16 Installation and Operation Manual GENERAL CONNECTION CIRCUIT OF ERACLE 16...

Page 29: ...ed by Contract reference Service intervals Monthly Quarterly Half yearly Annually ZONE LOCATION DETECTOR TYPE and QUANTITY PER ZONE Ion Ph RoR F T CP 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TOTAL Ion I...

Page 30: ...Zones Tested Faults Rectified Signature of Engineer Next Due 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Name FIRE A...

Page 31: ...dule 9 9 Plastic cap 21 4 Zone Expander 43ECZ020 ERACLE 16 Spare Parts Kit 10 Screw 3 6 DIN7985 4 11 Lightpipe for indication 1 12 EOL module 4 13 Jumper 1 4 Sounder Expander 43ECS020 ERACLE 16 Spare...

Page 32: ...18020929 RevB 02 2019 Comelit Group S p A Via Don Arrigoni 5 24020 Rovetta S Lorenzo BG Italy tel 39 0346 750 011 fax 39 0346 71436 www comelitgroup com info comelit it...