Mains pro 1.6.1 Global Guide
66
12.3.16 !dU Sig
Inverse immediate signaling relay – asymmetry; opens immediately in case of voltage (amplitude) unbalance,
positive sequence undervoltage, negative sequence overvoltage, or failure (over or under frequency). Relay
closes in case that all three methods of voltage asymmetry are in fail-free state, but no sooner than after
from its activation. If the relay is open during trip activation, it closes no sooner than Basic:
Imp Len since trip status activation. Fault reset has no influence on this output. If any asymmetry protection is
disabled by setpoint (limit set to 0), the output does not signal activation of this protection stage.
12.3.17 Other Sig
Immediate signaling relay – other failures; closes immediately in case of incorrect phase rotation, wrong polarity
of one phase or External trip. Relay opens in case that all observed failures are not active, but no sooner than
after
from its activation. If the relay is closed during trip activation, it opens no sooner
than Basic: Imp Len since trip status activation. Fault reset has no influence on this output.
12.3.18 !Other Sig
Inverse immediate signaling relay – other failures; opens immediately in case of incorrect phase rotation, wrong
polarity of one phase or External trip. Relay closes in case that all observed failures are not active, but no
sooner than after
from its activation. If the relay is open during trip activation, it closes no
sooner than Basic: Imp Len since trip status activation. Fault reset has no influence on this output.
12.3.19 Alt Sig
This output signals activation of binary input Alt Setting.This output is activated as long as alternative setting is
active and Alt setting is enabled.
12.3.20 TrpEndImp
Impulse at the end of the TRIP state. The output is normally activated during operation of the unit. The output
deactivates at the end of the
(i.e. after successful
is performed) for
period given by the parameter
In case of subsequent trip in the moment of the output deactivation, the countdown of the Imp Len delay is not
interrupted and the output stays deactivated for the complete Imp Len period. If in that period the TRIP state is
terminated again, the deactivation period is prolonged to Imp Len from the latest Fault Reset. If during TRIP
state the unit is disabled by the input
, the output TrpEndImp is deactivated, same as in case
of a successful Fault reset.
The output can generally be used for closing the circuit breaker by the ON coil.