Mains pro 1.6.1 Global Guide
57
V> neg, A.V> neg [V]
Threshold of the negative sequence overvoltage (angle asymmetry method).
Range
0.0..100.0 %Un
0
= OFF, the negative sequence overvoltage is disabled
Default setting
0.0 %Un = OFF
dU del, A.dU del [s]
Delay of the voltage unbalance (amplitude asymmetry) protection.
Range
0.00..600.00 s
Default setting
2.5 s
12.1.4 Group: f <>, A.f <>
f>, f>>, f<, f<<, A.f>, A.f>>, A.f<, A.f<< [Hz]
Threshold of 1st and 2nd stage overfrequency and 1st and 2nd stage underfrequency protection, respectively.
Range
45.00..65.00 Hz
0
= OFF, the appropriate stage of frequency protection is not enabled
Default setting
f>
0 Hz
f>>
52.00 Hz
f<
47.50 Hz
f<<
47.00 Hz
f> del, f>> del, f< del, f<< del, A.f> del, A.f>> del, A.f< del, A.f<< del [s]
Delay of the appropriate stage of the frequency protection.
Range
0.00..600.00 s
Default setting
f> Del
0 s
f>> Del
0.50 s
f< Del
20.0 s
f<< Del
0.50 s