MisfMAP reduct [ Bar ]
Required MAP value is immediately reduced by this value when binary input Misfiring is active.
Step:
0,001
Bar
Range:
-1,000 to 1,000 Bar
MisfLdRed del [ s ]
The engine load is reduced after
MisfLdRed del
when binary input Misfiring is activated.
Step:
1
s
Range:
0 to
Misfiring del
s
Misfiring del
[ s ]
Engine cool down protection is activated when binary input Misfiring is activated for
Misfiring del
.
Step:
1
s
Range:
MisfLdRed del
to 600 s
Knocking del
[ s ]
Engine shut down protection is activated when binary input DxLdReduct is activated for
Knocking del
.
Step:
1
s
Range:
0 to 600 s
MAP difference [ Bar ]
Allowed ± difference from MAP characteristic (
Low MAP
,
High MAP
).
Step:
0,001
Bar
Range:
0,000 to 1,000 Bar
MAP timeout
[ s ]
Engine shut down is activated when actual MAP is out of characteristics (
MAP difference
) for MAP
timeout.
Step:
1
s
Range:
0 to 600 s
kWh pulse
[ kWh ]
Number of kWh per one 1 sec pulse on Logical binary output “kWh pulse”. Pulse calculation starts
from setpoint change.
Step:
1 kWh
Range:
0 to 65535 kWh