InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-24
V Unb
V Unb
[%Un]
Threshold of the voltage unbalance (amplitude asymmetry). The value corresponds to the maximum
difference between highest and lowest RMS phase voltage of the 3-phase system.
Step:
1 % of nominal voltage
Range:
0 - 150 % of the nominal voltage
0 % = OFF the amplitude voltage asymmetry is disabled
Default setting: 20%
V< Pos
[%Un]
Undervoltage limit of the positive sequence.
Step:
0,1 %Un
Range:
0,0
–
100,0 % Un
Default:
1,0 % Un
V> Neg
[%Un]
Overvoltage limit of the negative sequence.
Step:
0,1 %Un
Range:
0,0
–
100,0 % Un
Default:
1,0 % Un
V Unb Del
[s]
Delay of the voltage unbalance (amplitude asymmetry) protection.
Step:
0,01 s
Range:
0,00 - 600,00 s
Default setting: 5,00 s
V Unb Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for voltage asymmetry protection.
Default setting: None
PhaseRotation [CW / CCW / ANY]
Direction of correct phase rotation.
CW:
clockwise
CCW:
counter-clockwise
ANY:
The protection is blocked, any phase rotation is possible
Default setting: CW
Ph Rot Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for phase rotation protection.
Default setting: None