InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-23
V <>
V>, V>>, V<, V<< [V]
Threshold of 1st and 2nd stage overvoltage and 1st and 2nd stage undervoltage protection
respectively.
Step:
1 V
Range:
1 - 34000 V
0 = OFF, the appropriate stage of voltage protection is disabled
Default setting:
V>
253 V
V>>
265 V
V<
200 V
V<<
184 V
V> Del, V>> Del, V< Del, V<< Del [s]
Delay of the appropriate stage of the voltage protection.
Step:
0,01 s
Range:
0,00 - 600,00 s
Default setting:
V> Del
1,00 s
V>> Del
0,50 s
V< Del
2,50 s
V<< Del
0,50 s
Rst V
[+/- 0% V<> , +/- 4% V<>, 95%NomVol]
Threshold for voltage measurement hysteresis.
Options:
+/- 0% V<>:
no voltage hysteresis is applied
+/- 4% V<>:
increase/decrease of the undervoltage/overvoltage limit by 4% of the limit
value
95%NomVol> reset value set to 95 % of the nominal voltage
Default setting:
+/- 0% V<>
Avg V >
[V]
Treshold of the 10 minutes floating average overvoltage
Step:
1 V
Range:
0 - 34000 V
0 - protection is disabled
Default setting: 253 V
V Trp BO
[Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for voltage protections.
Default setting: None