![ComAp InteliPro Installation And Operation Manual Download Page 77](http://html.mh-extra.com/html/comap/intelipro/intelipro_installation-and-operation-manual_2638971077.webp)
InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-21
Contr MailBox
E-
mail address used as “Sender” of alarm e
-mails from IB-Lite
H
INT
:
If SMTP server requires verification of sender, e-mail address has to be registered to SMTP server
and setpoints “SMTP UserName” and “SMTP UserPass” has to be setted to correct values.
Time Zone
List of time zones used for time reference.
DNS IP Address
IP address of Domain Name Server.
General
This group contains general setting of the unit and its protective functions.
ProtActiv Del
[s]
Common delay to activate for the protection stages set to PARALLEL after
inputs are closed. The delay applies in case of deactivation of
the protection stages that are blocked by these inputs.
Step:
0,1s
Range:
0
–
30 s
Default setting: 2,0 s
BackupTrp Del
Time period reserved for circuit breaker opening. If trip event occurs and the appropriate CB Feedback
does not deactivate within this period, the breaker is considered as "failed to open". Bak Com Trp
output is activated and in case that the functionality of CB backup are set-up, the appropriate actions
are taken.
Step:
0,01s
Range:
0,00
–
10,00 s
Default setting: 2,00 s
Comm Trp Del
Delay for Del Comm Trp output.
Step:
0.1 s
Range:
0.0
–
20.0 s
Default setting: 0,0 s
Comm Trp Len
Length of pulse on Del Comm Trp output after Comm Trp Del.
Step:
0.1 s
Range:
0.1
–
20.0 s
Default setting: 1,0 s
Auto FR
[DISABLED / ON DEACT / CB1+CB2=0 / DEL]
Setting of automatic fault reset functionality.
DISABLED:
AutoFaultReset is disabled
ON DEACT:
if at least one of the inputs CB1 Feedback or CB2 Feedback is deactivated,
AutoFaultReset is issued immediately
CB1+CB2=0:
if both CB1 Feedback and CB2 Feedback are deactivated, AutoFaultReset is issued
immediately
DEL: AutoFaultReset is issued in the moment when the measured values are within their
limits (no fault condition) no alarm is active plus the delay adjusted by AutoFR Del