InteliPro, SW version 1.4,
©
ComAp
–
April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-16
AIx Wrn/Trp Sig, IOM AIxWrn/Trp Sig
The outputs are activated in the moment when the appropriate protection threshold is exceeded
without any delay. The outputs stay active all the dime when faulty condition last. The outputs
deactivate when the AI value gets back within limits. Fault reset has no effect on these outputs.
BIx Status, IOM BIx Status
The outputs correspond to the status of the physical inputs of the unit or the IG-IOM or IGS-PTM
extension module respectively.
RemoteControl1 - 8
8 logical binary outputs, controlled via communication:
RemoteControl1
RemoteControl2
RemoteControl3
RemoteControl4
RemoteControl5
RemoteControl6
RemoteControl7
RemoteControl8
These outputs are controlled remotely by setting the value of communication object 10627
RemoteControl via communication. It is also possible to control them from
application.