InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
89
Analog inputs
13.6
Number of analog inputs
up to 3
Galvanic insulation
Not insulated
Electrical range
0-2500
Ω
Resolution
0,1 Ω
Supported sensor types
Predefined: VDO 10Bar, VDO Temperature, VDO Fuel level
User defined: 10 points non-linear sensors can be defined by the
user
Precision
2%
± 3 Ω
Generator/Mains measurements
13.7
Measurement inputs
3ph generator voltage, 3ph mains voltage
Measurement type
True RMS
Voltage range
480V Ph-Ph (277V Ph-N)
Max. measured voltage
340V Ph-N
Voltage accuracy
1 %
Current range
5 A
Max. measured current
10 A
Current accuracy
less than 2% from the range
Frequency range
40-70 Hz, measured from L1
Frequency accuracy
1 %
Charging alternator preexcitation circuit
13.8
Excitation current
100 mA
Charging fail threshold
80% of U
supply
Communication interface
13.9
USB (device)
On the board
CAN interface
13.10
Type
CAN bus
Galvanic insulation
No
Baud rate
250kbps
Bus length
max. 200m
Termination resistor
120Ohm, built-in, jumper activated
Type
CAN bus,
Baud rate
250kbps
Bus length
max. 200m