InteliNano-NT Plus, SW version 2.0.1.x,
©ComAp – July 2015
70
E10 Minimal Stabilization Time
Units:
seconds [s]
Step:
1 s
Range:
1
– 300 s
Default value:
3 s
Delay:
Minimum time after reaching of defined level of RPM to the closing GCB.
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Gen-set start failed – shutdown,
if the voltage or frequency are not in
the limit
On
Off
Time
Start
Engine run
Max. Stab. Time 7 s
Min. Stab. Time
Gen-set can be
loaded
Starter Output
Gen-set can be loaded
only when all running
condition are satisfied
E11 Starting RPM
Units:
%
Step:
1
Range:
5
– 60
Default value:
25
When Starting RPM are reached controller stops cranking. (Starter is disengaged.)