This input is used at a redundant controller to sense the "heart beat" from the
main controller. The input is to be connected to the output
the main controller.
If the redundant controller does not sense the heart beat from the main one,
it will activate the binary output
, which has to be wired in such
a way, that it disconnects the dead main controller, connects the redundant
controller instead and activates it.
N
OTE
:
Learn more about redundancy in separate chapter
Redundant controllers
.
13.2.1.79
Binary input: ForceValueIn 1
Related
FW
standard v3.1.0
Description This input activates the
Force value #1
block. If the input is active, the value of the
setpoint, to which the Force value #1 block is configured, will be overriden by value of
the alternative setpoint assigned to the Force value #1 block.
N
OTE
:
If there are more than one force value blocks configured onto one setpoint then the
highest priority has the block with the lowest index (i.e. the first active block according
to the list displayed in GenConfig in the Force value window at the related setpoint).
N
OTE
:
Watch a training video about force value function here:
http://www.comap.cz/support/training/training-videos/