11.2.10.9
Setpoint: Load gain
Group
Sync/Load Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the gain factor (P-factor) of the load control PI loop. The
integration factor (I-factor) for the load control loop is adjusted by the setpoint
A
PPLICATION
L
OAD GAIN AND
L
OAD INT SETPOINTS ARE ACTIVE DURING
:
MCB,
MGCB
parallel to mains operation in any mode where IM-NT
load control loop is active (see setpoint MLoad ctrl PtM),
including load ramps
BTB
BusLeft or BusRight BaseLoad control in any mode
where IM-NT load control loop is active (see setpoint
MultiLoad ctrl), including load ramps
N
OTE
:
When this setpoint is set to zero, the corresponding control loop is switched