InteliMains 210 Global Guide
482
Related FW
2.0.0
Related applications
MCB, MGCB, BTB
Comm object
9981
Description
Logical analog input designed for general value received from analog sensor. Limits for this protection are
adjusted by setpoints
Analog Protection 19 Wrn (page 243)
and
Analog Protection 19 Sd (page 243)
. Delay is
adjusted by setpoint
Analog Protection 19 Delay (page 243)
.
Monitoring
Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl
Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
AL Indic
Analog value is not used for protection. Only alarmlist record is made if analog
value is out of the limits.
Wrn
Analog value is used for warning protection only.
Wrn+Stp
Analog value is used for warning and slow stop protection
Stp
Analog value is used for slow stop protection
Wrn+BOR
Analog value is used for warning and breaker open protection
BOR
Analog value is used for breaker open protection
Protection types
Note:
This parameter has to be adjusted via InteliConfig.
Under limit
Alarm is activated when value of analog input is under adjusted limits
Over limit
Alarm is activated when value of analog input is over adjusted limits
Under limit + fls
Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls
Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example:
Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be act
Sensor fail alarm will be activated.
Note:
This parameter has to be adjusted via InteliConfig.
AIN Prot19