InteliMains 210 Global Guide
202
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
1,2 .. 32 [-]
Default value
1 s
Alternative config
NO
Step
1 s
Comm object
10591
Related applications
MCB, MGCB
Description
If the input
of this particular controller is used to provide the "group link" information
for two Control groups (to get more information refer to the chapter
), then this
setpoint is used to select which group is located at the right side of the group link breaker (bus tie breaker). If
this particular controller is not used for the group link function, adjust this setpoint to 1.
Group Link R
Group: Load Control
Subgroup: Regulation Loops
Setpoint group
Load Control
Related FW
2.0.0
Range [units]
0,0 .. 200,0 [%]
Default value
10,0 %
Alternative config
NO
Step
0,1 %
Comm object
8715
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts the gain factor (P-factor) of the frequency control PI loop.
Note:
See the chapter
for more information.
Frequency Gain
Setpoint group
Load Control
Related FW
2.0.0
Range [units]
0 .. 100 [%]
Default value
50 %
Alternative config
NO
Step
1 %
Comm object
8716
Related applications
MCB, MGCB, BTB
Description
This setpoint adjusts the relative integration factor (I-factor) of the frequency control PI loop.
Note:
See the chapter
for more information.
Frequency Int