InteliMains 210 Global Guide
197
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
#Starting Rel Load Reserve 2 (page 196)
.. 110 [%]
Default value
80 %
Alternative config
NO
Step
1 %
Comm object
10653
Related applications
MCB, MGCB
Description
This setpoint is used to adjust the load reserve for stop of next gen-set in relative mode. i.e.
= REL.
IMPORTANT: Logical binary input
has to be activated,
otherwise setpoints of Load Reserve Set 1 are used.
Note:
See
chapter for more information.
#Stopping Rel Load Reserve 2
Subgroup: Minimal Running Power
Setpoint group
Power Management
Related FW
2.0.0
Range [units]
0 .. 65 000 [kW]
Default value
210 kw
Alternative config
NO
Step
1 kW
Comm object
9584
Related applications
MCB, MGCB
Description
This setpoint is used to adjust certain minimum value of the sum of nominal power of all running gen-sets. If
the function is active (by logical binary input
Min Run Power Active (page 430)
), then the gen-sets would not
be stopped, although the reserve for stop is fulfilled, if the total remaining nominal power drops below this
minimal value.
Note:
Logical binary input
Min Run Power Active (page 430)
) needs to be activated on all gen-sets in the
same time.
#Min Run Power