InteliMains 210 Global Guide
172
Subgroup: Transferred Bus Power Measurement
Setpoint group
Process Control
Related FW
2.0.0
Range [units]
None/Mains CT/Analog Input [-]
Default value
Mains CT
Alternative config
NO
Step
[-]
Comm object
10599
Related applications
MCB, MGCB, BTB
Description
Defines source value of the
measurement.
None
The Transferred Bus Power is not measured.
Bus CT
The
value is measured via Bus CTs.
Analog Input
The
value is measured via analog input, accordingly LAI:
Bus Power Measurement
Subgroup: BTB Control
Setpoint group
Process
Control
Related FW
2.0.0
Range [units]
Enabled / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
16047
Related applications
BTB
Description
Setpoint for adjustment of the direction of synchronization. This setpoint has to be Enable for situations
where the Mains is on the left side and gen-sets are on the right side.
Note:
In case the Mains is on the right side, the controller will not try to synchronize.
Synchronization R To Mains