InteliLite Global Guide
85
Breaker open and cool down (BOC)
The event appears in the alarmlist and is recorded into the history log. It causes immediate opening of the GCB
and then the standard stop sequence with cooling follows. The gen-set cannot be started again while there is a
BOC alarm in the alarmlist. Activates the output
as well as the standard alarm
outputs (
and
).
Sensor fail detection (FLS)
If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the
. The valid range is defined by the most-left (RL) and
most-right (RH) points of the sensor characteristic ±12.5% from RH-RL.
Note:
Sometimes there can be problem with lower limit of valid range which can be counted as negative
number. In this case the lower limit is set as one half of the RL point of the sensor curve characteristic.
Image 5.17 Sensor fail detection principle
Remote alarm messaging
If communication plug-in module is connected to the controller, the controller can send SMS messages and
emails at the moment when a new alarm appears in the
or new event is written in
. The message will contain a copy of the
or reasons from
To enable this function, you should select adjust setpoints
,
,
and
to select the types of messages. Also enter a valid GSM
phone number or email address to the setpoints
,
,
Email Address 1 (page 326) Email
Address 2 (page 326)Email Address 3 (page 327)
, and
.
The list of all supported terminals shows the table below:
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...