InteliLite Global Guide
593
Related applications
AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
adjusts the short current limit
Short Circuit BOC Delay (page 195)
adjusts the delay in fine steps
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Start Fail
Alarm evaluated
When the gen-set is being started
Related applications
AMF, MRS
Description
This alarm will be issued after all attempts to start the gen-set have run out but the
gen-set did not start. The following setpoints are related to this alarm:
adjust the number of attempts
Sd Start Fail
back to List of alarms level 2
Alarm Type
Shutdown
Alarmlist message
Sd Underspeed
Alarm evaluated
Engine running only
Related applications
AMF, MRS
Description
This alarm will be issued when the gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint
.
The underspeed alarm starts to be evaluated after successful gen-set start and is
being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed
back to List of alarms level 2
Other type
Alarm Type
BOC
Alarmlist message
BOC Coolant Temperature
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in
Coolant Temperature Sd (page 179)
setpoint.
BOC Coolant Temp
Summary of Contents for InteliLite MRS16
Page 40: ...InteliLite Global Guide 40 4 4 12 Example of MRS Wiring ...
Page 55: ...InteliLite Global Guide 55 ...
Page 56: ...InteliLite Global Guide 56 ...
Page 57: ...InteliLite Global Guide 57 ...
Page 58: ...InteliLite Global Guide 58 ...
Page 59: ...InteliLite Global Guide 59 ...
Page 60: ...InteliLite Global Guide 60 Setpoint Screens ...
Page 61: ...InteliLite Global Guide 61 History Log ...
Page 62: ...InteliLite Global Guide 62 ...
Page 63: ...InteliLite Global Guide 63 ...
Page 64: ...InteliLite Global Guide 64 ...
Page 65: ...InteliLite Global Guide 65 5 3 3 Browsing alarms ...
Page 66: ...InteliLite Global Guide 66 5 3 4 Password Enter password ...
Page 67: ...InteliLite Global Guide 67 Change password ...
Page 68: ...InteliLite Global Guide 68 Note Use Up and Down button to select required level of password ...
Page 69: ...InteliLite Global Guide 69 Log out from controller ...
Page 71: ...InteliLite Global Guide 71 5 3 6 Language selection ...
Page 72: ...InteliLite Global Guide 72 ...
Page 78: ...InteliLite Global Guide 78 Image 5 13 Flowchart of start of diesel engine ...
Page 80: ...InteliLite Global Guide 80 Image 5 14 Flowchart of start of gas engine ...
Page 582: ...InteliLite Global Guide 582 more information see Alarm types Level 2 on page 84 ...