InteliLite 9 Global Guide
370
Related applications
AMF, MRS
Description
The controller detects phase sequence on generator voltage terminals. This
protection is important after controller installation to avoid wrong voltage phase
connection. There is a fixed defined phase sequence in InteliLite 9 controller: T35 =
N, T36 = L1, T37 = L2 and T38 = L3. When the phases are connected in a different
order, alarms are detected. This alarm prevent circuit breaker closing.
back to List of alarms level 1
Alarm Type
Alarm indication
Alarmlist message
Mains CCW Rotation
Alarm evaluated
All the time
Related applications
AMF
Description
The controller detects phase sequence on mains voltage terminals. This protection
is important after controller installation to avoid wrong voltage phase connection.
There is a fixed defined phase sequence in InteliLite 9 controller: T39 = N, T40 =
L1, T41 = L2 and T42 = L3. When the phases are connected in a different order,
alarms are detected. This alarm prevent circuit breaker closing.
Mains CCW Rotation
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Manual Restore
Alarm evaluated
All the time
Related applications
AMF
Description
Alarm is activated when controller is in AUTO mode,
setpoint is set to manual, load is on gen-set a mains has returned.
Manual Restore
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
Module(slotA) - comm. outage
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
Module(slotA) - comm. outage