InteliLite 9 Global Guide
369
Alarm Type
Other
Alarmlist message
EM(A) - a message lost
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(A) - a message lost
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
EM(A) - configuration mistake
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with configuration of binary input or
output of module in slot.
EM(A) - configuration mistake
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
EM(A) - insufficient
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted in setpoint
and email wasn’t
send.
EM(A) - insufficient
back to List of alarms level 1
Alarm Type
Other
Alarmlist message
EM(A) - missing or damaged
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in slot
(in first 5 second there was no communication and module is configured in slot).
EM(A) - missing or damaged
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Generator CCW Rotation
Alarm evaluated
All the time
Generator CCW Rotation