Alarm Type
Warning
Alarmlist message
Wrn Generator < Frequency
Alarm evaluated
Generator excited only
Related applications
AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency Wrn (page 196)
Generator <> Frequency Delay (page 196)
Wrn Generator < Frequency
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn Check DPF Status
Alarm evaluated
When ECU is configured
Related applications
AMF, MRS
Description
This alarm occurs when ECU send alarm message about Tier IV protection.
Note:
Tier IV protection have to be supported by ECU.
Wrn Check DPF Status
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn Mains Voltage Detected
Alarm evaluated
Gen-set is running
Related applications
AMF
Description
This alarm occurs when setpoint
is adjusted to MRS
and voltage is detected on mains.
Wrn Mains Voltage Detected
back to List of alarms level 1
Alarm Type
Warning
Alarmlist message
Wrn Maintenance 1
Alarm evaluated
All the time
Related applications
AMF, MRS
Description
Adjust the setpoint
Maintenance Timer 1 (page 187)
to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. The alarm message will
remain in the alarm list (even if the controller is switched off and on again) until the
setpoint is re-adjusted to a positive value.
Wrn Maintenance 1